Clearance Sheet M2016-002136

 Department IssuesSigned OffIntl

1)Sheet 000 general notes 1 and 2 reference the wrong code cycle.

5/12/2016 jadams

2)Please provide product approval sheets

5/12/2016 jadams

3)Door 107 B does not comply with 320.1.1 of the 2014 FBC-R

5/12/2016 jadams

4)Please provide a current elevation certificate for this building as this renovation will trigger the substantial improvement requirements from FEMA.

5/12/2016 jadams

5)Please provide a clearance sheet and an approved site plan which complies with 107.2.5 of the 2014 FBC

 

6) Sheet E 201 shows a 20 amp panel please explain

5/12/2016 jadams

7)Please provide smoke detectors and carbon monoxide detectors on the electrical layout.

5/12/2016 jadams

8)Please provide water proofing details for rear porch.

5/12/2016 jadams

9)Please provide energy sheets for this building as applicable.

 

10)Please explain the design code reference to the 2014 FBC -Residential as this is a condo building per the property appraiser web site

5/12/2016 jadams

11)Review is incomplete at this time

5/12/2016 jadams
General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal.
If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again.
ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.