| | Department Issues | Signed Off | Intl |
|
|
1)These comments are for the entire building.
|
9/30/2015
| blaw |
|
|
2)sheet a 1.0 indicates that this a 7 unit townhome however it is a 6 unit, please revise.
|
9/22/2015
| blaw |
|
|
3)Sheet a3.3 excerpt of 806.1 appears to be incorrect, please review and revise
|
9/22/2015
| blaw |
|
|
4)The roof vent locations do not appear to be iaw 806.2 on sheet a3.3
|
9/22/2015
| blaw |
|
|
5)Please provide typical wall details showing siding applications as the majority of ones provided are for stucco.
|
9/22/2015
| blaw |
|
|
6)Sheet a3.3 shows ridge vents being used in conjunction with off ridge vents, please review and revise.
|
9/22/2015
| blaw |
|
|
7)Please provide the rated walls that extend past the 2 hour separation walls on the zero lot lines.
|
9/22/2015
| blaw |
|
|
8)Please explain with code references that allow overhangs past the lot line.
|
9/22/2015
| blaw |
|
|
9)Please review the exposed wall perimeter on the energy sheets for the garage.
|
9/30/2015
| blaw |
|
|
10)Please identify powder door size on sheet A4.2.1
|
9/22/2015
| blaw |
|
|
11)Please review the water heater locations as the ones in the interior units are shown in the garage, however the energy sheets indicate exterior on all six units.
|
9/30/2015
| blaw |
|
|
12)Please explain in detail how to vent the water heaters in the garage iaw the manufacturer instructions, provide minimum separation to electrical components and all applicable information.
|
| |
|
|
13)Please review the reference 1/AD1 as a U336 wall, this reference is at the garage wall throughout the plans.
|
9/22/2015
| blaw |
|
|
14)Please explain the batten and board at the front of the building on the product approval sheet (hardi panel?)
|
9/30/2015
| blaw |
|
|
15)Please provide the installation instructions for the brand of the shaft liner system to be used at the 2 hour separation wall from the manufacturer.
|
9/30/2015
| blaw |
|
|
16)Truss FG03 appears to be missing a center bearing support at the stairway, please review this truss
|
9/30/2015
| blaw |
|
|
17)Please show compliance with table R302.1(1)of the 2014 FBC-R as it applies to the rear porches.
|
| |
|
|
18)The 1 hour wall section on sheet AD.5 does not show the 5/8" Densarmor extending to the roof deck, please revise drawing.
|
9/30/2015
| blaw |
|
|
19)Smoke detectors are not referenced in section 313 of the 2014 FBC-Res as stated on the electrical layouts, please review and revise as necessary.
|
9/30/2015
| blaw |