1. T12 Truss Bracing: Detail S2.1D detail 14 shows bracing that penetrates the tenant separation wall. Please revise the detail to terminate the bracing at the exterior of the drywall.
|
| |
|
|
2. T16, T17, and T18: The interior bearing of T16, T17, and T18 occur in the tenant separation wall. Please revise the bearing to occur on the outside of the tenant separation wall.
|
| |
|
|
3. Solatube: Please provide state product approval for the Solatube.
|
| |
|
|
4. Energy Form: Please revise the energy form: (1)Indicate foam plastic at the attic roof deck. (2) Provide the ES report for foam plastic that is proposed and indicate which application will be used. (3) A separate energy form for each unit (FBC-R N1100.06)
|
| |
|
|
5. Attic Truss Tenant Separation: The proposed tenant separation at the attic truss is incorporating the wall assembly U314. Please provide an assembly that has been tested with a roof truss or use the time assignment from FBC Table 721.6.2(1)
|
| |