SJC Home
Clearance Sheet C2026-001673

 Department IssuesSigned OffIntl

Plans for a 573 head NFPA 13 fire sprinkler system for a new 2 story educational facility.  The system has 2 separate risers: Riser 1 which covers the southern wings and gymnasium with a remote FDC, and Riser 2 which covers the northern wings and has a wall mounted FDC.  The system is designed with 4 remote areas as Light hazard .10 density. 


                                                        
Reviewed using FFPC 8th edition effective Dec. 31, 2023.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed. NFPA 1:1.12.4</span

 

1) Per the approved fire main plan, both risers have yard FDC's.  Riser 2 is indicated to have a wall FDC.  Ensure that you plans match the approved underground plans.    

 

2) Unable to locate air vent on the plans in accordance with NFPA 13:8.1.5, if provided please callout on the plans. 

 

3) Hydraulic calculations for remote area 2 were provided twice.  Provide hydraulic calcs for remote area 3.  NFPA 13:27.4.1.

 

4) If you are installing the EZPac trim with the built in pressure release, indicate this on the plans.  Or otherwise provide the pressure release as required by NFPA 13:8.1.2.1.

 

5)  Provide spec sheet for suspended ceiling tile grid showing it meets ASTM C635/C635M. NFPA 13 17.4.1.3.3.2.   Flexible sprinklers shown in product data. 

 

6) Provide FDC signage for each yard FDC indicating which riser is supplied (1 or 2) and which geographical portion of the building is supplied by description.  Example: Riser 1- South Wings/Gymnasium (or similar)  Riser 2- North Wings/Administration (or similar).  In addition provide signage on both riser room walls or doors facing the FDC's that match the FDC signs.

 

7) Provide note on FP-01A indicating that Waiting 100 will be covered from above similar to the notes for Gymnasium and Chapel. 

 

8) No head indicated at the top of the elevator shaft.  Cite exemption per NFPA 13:9.3.6.