SJC Home
Clearance Sheet C2026-001673

 Department IssuesSigned OffIntl

Plans for a revision that came in 3 rolls, a single roll with less sheets, and 2 rolls that are a little larger with more sheets.  Per the revision request sheet, "Sheet E-101.1a- updated include the second means of egress.  FA sheets included in this revision."

First Roll- contains the following sheets- E-101.1a- Only 1 copy provided, the second means of egress is not indicated.  FP-101.1- Not included in narrative, appears that site piping information was added to the site plan, and the flow/pressure chart was updated.  A-101.1.a- Not included in narrative, only 1 copy provided,  shows added 2nd means of egress.  No FA sheets. 

Second Roll- Contains A-001, A-010.1, A-010.1.1, A-010.2, A-101.1.a, A-101.2.a, A101.3, A102.1.a, A-601, E001.1, E002.4, E-601.2, E602.1, E002.1, E-101.1.a, E-101.1.b, E-101.1.c, E-102.1.a, E-102.1.b, E-301.1, E-501.1, E-604.1, E-701.1, E-701.2, FP-101.1, M-101.1.a, and FP-101.1.

Third Roll- Same as second roll except: A101.1.a not provided, 2 copies of E-101.1.a provided, second copy of FP-101.1 not provided.     


                                                        
Reviewed using FFPC 8th edition effective Dec. 31, 2023.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed. NFPA 1:1.12.4</span

 

1) Provide an itemized revision narrative for all provided sheets.  Remove any sheets that are not intended to be included.  Provide 2 identical plan sets for review.