405.3.2 Public lavatories.
In employee and public toilet rooms, the required lavatory shall be located in the same room as the required water closet.
The lavatory vestibule does not meet the requirements of the provided code. Please show the required lavatories with in the room where the required lavatories are located.
|
8/21/2026
| ccrain |
|
|
Panel HA is shown on the panel schedule but is missing from the riser schedule. Please add
|
| |
|
|
The 400 amp MBA is not shown in the panels schedule. Please provide.
|
| |
|
Informational
|
Preliminary reviews are one time reviews submitted prior to approval of a clearance sheet and site plan. Because of this, and the documentation and plans are usually insufficient and incomplete, a full review cannot be accomplished without the possibility of adding additional comments at time of future submittals.
|
| |