7) Plans Sheet G-003 indicate there will be hazardous materials stored on site (9/G-003). Some information was provide. Additional information is needed.
Provide completed Hazardous Materials Inventory Statement in accord with NFPA 1:60.1.6, (See Section II (Hazardous Materials Inventory Statement) of “Hazardous Materials Management Plan” Annex C.3.1 of NFPA 400 (400:1.12.1), 2019 Edition. If material quantities exceed MAQ be prepared to show compliance with appropriate section of hazardous materials code (NFPA 1 Ch.60).
Guidance: Make sure to include hazard class(es) in accord with NFPA 1, and any sub classes so I am able to check the designers work to make sure chemical's requirements met. Not all chemicals are hazardous and not all hazardous chemicals will have sub classes. Some chemicals can also fall into one (1) or more hazard classes. If you need someone to guide your project with chemicals to meet Code you may need to reach out to an Industrial Hygienist or Fire Protection Engineer.
Below is a list of the hazard classes and sub classes.
-Aerosols: Level 1-3, cooking spray Plastic Aerosol: Level 1,3, or X.
-Compressed gas or Cryogenic fall
-Corrosive solid or liquid
-Explosive, fireworks, model rocketry
-Flammable or combustible liquids: Flammable: Class IA, IB, or IC Combustible: Class II, IIIA, or IIIB
-Flammable solids
-Highly toxic, toxic solids and liquids
-LPG or LNG
-Oxidizer solid and liquid: Class 1-4
-Pyrophoric solid and liquid
-Unstable reactive solid and liquids
-Water reactive solid and liquid
-Ammonium nitrate
-Organic peroxide solid and liquid: Class I-V