Clearance Sheet C2025-001571

 Department IssuesSigned OffIntl

Plan reviewed for the fire underground Daily's at Silverleaf. The underground will be in 2 Phases. This is only for the backflow and private fire hydrant. THIS is considered PHASE 1.

This originally was included on Comm 24-114 which was approved  on April 14, 2025. There was a MODCP 25-64 which includes a medical office on the adjacent property. This medical office will be sprinklered. (C25-1620). This will be Phase 2.

The underground for this project(Daily's is shown on both the COMM 24-114 and the MODCP 25-64.

8" Zurn Model 350DA DCDA with freeze protection

8" PVC C900 DR-18

8"x 6" reducer

6" Gate Valve and Valve Box

6" (RED) Waterous Private Fire Hydrant.

Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: J.L. Hatcher 904-209-1741, jlhatcher@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

10/17/2025 jlhatcher