Plan reviewed for 8" Private fire main:
8"x 8" Tapping sleeve
8" DR-18 Pipe
8" DCDA BFP- This insulated BFP will be electronically supervised. Conduit provided from BFP to Panel
6" Private hydrant provided with control valve and will be painted red.
6" FDC- This insulated FDC will have a Wafer check and 5" Storz with downward 30 degree deflection.6" supply piped from the FDC to inside the riser room
8" Riser piped 1' AFF inside riser room.
Received and reviewed material submittals
Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: J. Hatcher 904-209-1741, jlhatcher@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.