Clearance Sheet C2024-005628*005

 Department IssuesSigned OffIntl

Plans for a revision to sheet FA-01 through FA-10.  The revision is indicated as Delta 2 dated 03/26/26. There are a couple changes from the last plan on sheet FA-04 that are labeled as Delta 1 that appear that they should be Delta 2.  They are highlighted and included in this review.  Also the hold on the permit for comment 5 to be addressed for the traction control elevator heat has been signed off.  Both heats have been removed but they are not required since the elevator is not sprinklered per NFPA 72:21.4.


                                                        
Reviewed using FFPC 8th edition effective Dec. 31, 2023.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

4/16/2026 PWebb