 Department IssuesSigned OffIntl

Plans for a revision to the following sheets:GO20B, A2011B1, A2012B1, A2013B1, A2014B1, A2021B1, A2021B2, A2022B1, A2022B2, A2023B1, A2024B1, A2033B1, A500B, A501B, A502B, A503B, A504B, A506B, A508B, A511B, A512B, A514B, A515B, A6011B, A6012B, A6013B, A6014B, A6021B, A6022B, A6023B, A6024B, A603B, A604B, A610B, A611B, A612B, A900B, A901B, I001B, FP201B, FP2011B, FP2021B, P010B, P2011B1, P2012B1, P2013B1, P2014B1, P2022B1, P2024B1, M2011B1, M2011B2, M2012B1, M2013B1, M2021B1, M2022B1, M2023B1, M2033B1, E010B, E2011B1, E2011B2, E2011B3, E2012B1, E2012B2, E2012B3, E2O13B1, E2013B2, E2013B3, E2021B1, E2021B2, E2021B3, E2022B1, E2022B2, E2022B3, E2023B1, E2023B2, E2023B3, E2024B1, E2033B3, E5001B, E6002B, E8003B, E9001B, E9002B, T2011B, T2012B, T2013B, T2021B, T2022B, T2023B, t3001B, SC201B, SC201B.1, and SC2011B. 

A detailed itemized revision narrative has been provided. 


                                                        
Reviewed using FFPC 8th edition effective Dec. 31, 2023.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.

 

1) One of the revised notes on sheet E2012B1 indicates "Revised lighting controls in corridors to be controlled via time switch panel located in electrical room rather than ceiling mounted occupancy sensors.  Minor circuit revisions made to light fixtures."

My question is whether or not this change will meet NFPA 101:7.8.1.2.2 (4) which states "The lighting control device is activated by any occupant movement in the area served by the lighting units"

-------------------------

Thursday, October 30, 2025 PJW- I spoke to Hassan with TLC Engineering regarding this.  I explained the different options that they have, and the requirements for the lighting.  He understood and will resubmit with a resolution depending on Baptists preference.