Plan Rejected for underground fire main for Building 4: 266,242 SF warehouse and Building 5: 280,801 SF warehouse.
- Connecting to existing 12" water main
- 12" RPDA BFP
- 12" DR-18 pipe connecting to fire pump
- 10" DR-18 pipe coming out of the fire pump building.
- 10" fire main around entire site. (Boosted by fire pump)
- 10 fire hydrant assemblies.
Both buildings 4 and 5 fire sprinkler systems are going to be supplied in the same manor:
- Teeing off of 10" fire main with 10"x6" tee in 6 locations.
- 6" gate valve
- 6" DR-18 fire main
- Each building has 3 separate 6" in-building risers finishing 1' AFF.
Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: Stuart Schnellenberger 904-209-1778, SSchnellenberger@SJCFL.US
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.