| 
                                        Clearance Sheet C2023-007918 | 
                                    
                                 
                                
                                    | 
                                        
                                     | 
                                 
                                
                                    
                                        
    
    
    
    
            
                
                
             
            
	
		
			|   | Department Issues | Signed Off | Intl | 
		 
			| 
                            
                         | 
                             Plan reviewed for 18,046 SF Type IIIB(III(200)) Construction, Fully sprinkled, Fire Alarm w/Voice Evac. 
1st Floor: 15,077 SF including 6,023 Sf Event Space and 2,386 SF Lobby. 
2nf Floor: 2,969 SF including 9 storage rooms. 
Classification of Hazard of Contents: Low Hazard 
Reviewed as Existing Assembly (1st FL) and Storage (2nd FL). Chapters 43, 13 and 42 of NFPA 101.
  Reviewed using FFPC 7th edition effective Dec. 30, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC. 
Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code. 
----------------------------- 
Friday, April 26, 2024 DF: Met with the building owner regarding among other things the FFPC Edition. It was decided by Fire Marshal Rob Dowling that since the Clearance Sheet application was started on 12/21/2023 that the 7th Edition of the FFPC will be the edition the review will be under. 
----------------------------- 
Wednesday, June 19, 2024 DF: Review of 1st Resubmittal. ALL Sheets have been replaced. 
Thursday, June 20, 2024 1300 hrs. DF: Spoke with Architect Conner Dowling via phone regarding the classification of this building as Historical. After discussion, Mr. Dowling stated that he is going to classify this building as Historical with work falling under NFPA Chapter 43.10.1(2) which will utilize Sections 43.3, 43.4, 43.5, 43.6, and 43.7 as they relate according to 101:43.10.1(2). 
----------------------------- 
Tuesday, July 30, 2024 DF: Review of the 2nd Resubmittal. 
                         | 
                            7/30/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             RESUBMITTING: A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8". - Code responses shall reference Florida Fire Prevention Code, 8th Ed. 
                         | 
                            7/30/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             1) Code Information on Sheet G101 shows the 7th Edition of the Florida Fire Prevention Code (FFPC). The current edition of the FFPC is the 8th Edition, which includes the 2021 Florida Editions of NFPA 1 and NFPA 101. 
Update the Code Summary to reflect the correct edition of the FFPC and verify the plans have been drawn to the current edition of the FFPC. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Drawings have been submitted before the code change on 12/31/2023. 
Wednesday, June 19, 2024 DF: Reviewer's Response: Per Fire Marshal Dowling on 04/26/24 ruled that the 7th Edition will be the governing edition of the FFPC (see review Header Above). 
                         | 
                            6/19/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             2) The plans identify numerous Florida Building Code (FBC) references. Provide corresponding and/or parallel Florida Fire Prevention Code (FFPC) references. Point out the more stringent code reference. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: See G101 Revision 1. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             3) Code Summary on Sheet G101 states: “Building Has Historic Designation Status”. If the intent is to utilize the “Historic Buildings” section of NFPA 101, Chapter 43, Subsection 10 of Building Rehabilitation (101:43.10), you will need to have your registered design professional prepare a written report (evaluation) in accordance with NFPA 101:43.10.2 and provide such report to the Fire Marshals Office for review. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: See submitted report(s) with Revision 1 documents. 
Wednesday, June 19, 2024 DF: Reviewer's Response: A letter from Dr. Kayra N. Lucas, Supervisor Survey, Registration, and Technical Services Bureau of Historical Preservation, Florida Department of State providing information regarding the Historical Status and uses of the building. The letter calls out the historical status of the building and appears to provide some relief from ADA requirements and calls out how the 1st floor is being largely preserved and rehabilitated as an event hall and the 2nd story portion is to be maintained as unoccupied, publicly inaccessible storage. 
This letter is being scanned into this permits archive. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             4) In Building Radio Enhancement System (BDA) See also FS633.202(18) 
The third-party contractor must conduct a two-way radio communication test in accordance with NFPA 1:11.10 and NFPA 1225. 
 
  
St Johns County Fire Rescue’s radio control frequency is 853.8875.  
You will need to submit a revision prior to the 105 framing inspection to have the hold removed. 
-If it passes the inspection radio testing, you will need to submit as a revision so we can record the passing test and remove the hold.  - If the third-party paperwork indicates the test is not satisfactory, the revision will need to include: the unsatisfactory test paperwork, outline of corrective measures, and plans to illustrate the corrective measures to meet requirements provided by the design professional. Then at the final, you will be required to provide satisfactory testing by the third-party contractor following the installation of the in-building radio enhancement system. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Contractor to coordinate. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             5) The last known occupancy/use of this building was mercantile. The current proposed use is assembly. A change of occupancy/use review is being conducted for the building including both 1st and 2nd floors. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Current Occupancy is assembly "rental venue". 
Wednesday, June 19, 2024 DF: Reviewer's Response: Business tax receipts from the former City of Hastings was presented to the Fire Marshals Office showing that is was an auction House / Assembly. The Fire Marshal has approved the us as existing. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             6) What is the classification of Hazard of Contents for the Assembly and Storage Occupancies? 101:12.1.5, 101:42.1.5  
Provide the classification of Hazard of Contents for both the Assembly and the Storage Occupancies. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Classified as S-2, Low Hazard Storage. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             7) Based on construction type IIIB / III(200) and Construction Type Limitations Table 12.1.6 (101:12.1.6), The maximum occupant load for the 1st floor is 1,000 persons or less.  
Occupant load provided (not counting storage and like rooms) is 1,110 Occupants.  
Event room:861, RR Lounge:25, Prep Kitchen:7, Back Bar: 2 Front Bar:2, Groom Lounge:26, Bridal Lounge:27, Lobby:160. 
Utilizing the FFPC, how will you reduce the occupant load to 1,000 occupants or less (including total occupants for the 1st floor)? 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Please see G101 Revision 1 for reference to NFPA 101 Chapter 13 provisions for existing assembly occupancy. 
Wednesday, June 19, 2024 DF: Reviewer's Response: As the assembly occupancy has been deemed existing the existing occupancy occupant load on the 1st floor is permitted per 101:TABLE 13.1.6. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             8) Provide the separation of occupancies (Assembly/Storage) in accordance with NFPA 101 Chapter 6. 101:6.1.14.4.1. Including the separation between the assembly below and the storage above. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: 1 hour floor assembly separation between existing S-2 and lobby below, See assembly C53 on G102 and notes on A101 and A151. 
Thursday, June 20, 2024 DF: Reviewer's Response: Sheet G101 identifies the stair walls as one (1) hour fire rated. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             9) Missing Mechanical and Electrical Sheets. Sheet CS lists these Sheets as deferred submittals. However, these Sheets are required to be provided at time of the plans review. 
Provide the missing Mechanical and Electrical Sheets. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Provided in Revision 1 Submission. 
Wednesday, June 19, 2024 DF: Reviewer's Response: I am not able to locate any Mechanical Sheets. Provide missing Mechanical Sheets. 
----------------------------- 
Tuesday, July 30, 2024 DF: RTC: Please see updated full sized mechanical sheets submitted in REV 2. 
                         | 
                            7/30/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             10) Missing the Fire Protection Sheets. An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided.  It is not a full set of shop drawing. FAC 61G15-32.004 
Provide missing Fire Protection Sheets. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: 61G Provided with Revision 1 documents. 
Wednesday, June 19, 2024 DF: Reviewer's Response: I am not able to locate any Fire Protection Sheets and / or 61G15-32.004 information. 
----------------------------- 
Tuesday, July 30, 2024 DF: RTC: Please see submitted 61G15 submitted in REV 2. 
Tuesday, July 30, 2024 DF: Reviewer's Response: 61G15-32.003 & 61G15-32.004 provided on 8.5" x 11" Sheets by HAZARD Fire Protection Engineering, Inc. The 61G15 document is digital / NOT Wet Signed. I am not able to verify the signature. 
Please provide a wet sealed and signed 61G15 document. 
Tuesday, July 30, 2024 1320 hrs. DF: Spoke with Architect Conner Dowling via phone. Conner agreed to place a HOLD 105 Revision to Provide an updated wet signature FP Sheets. 
                         | 
                            7/30/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             11) The 2nd floor plan differs between this permit submittal and the 2nd floor plan submitted for an emergency outside egress stair (permit #12200063 - CC’d 09/06/2023). In this submittal (Sheet G102), The bathroom is no longer shown, rooms have been reconfigured and the interior stair is relocated and redesigned from what is shown in the archived permit sheet #A1. 
Provide architectural sheets (and others such as MEP’s as needed) demonstrating the correct floor layout, changes that have been made, interior stair construction, lighting (including emergency lighting), electrical, mechanical, new and existing. 101:42.2.2.3, 101:7.2.2 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: See letter from Les Thomas, Architect for previous permit. 
Wednesday, June 19, 2024 DF: Reviewer's Response: New Sheets have been submitted. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             12) It is noted that the 2nd Floor is only accessible from the exterior of the building with no access from the interior. 
a) Is it the intent the 2nd floor will or may be occupied by a separate tenant or business? 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: No, the 2nd floor is intended to remain unoccupied per G102. All storage at 2nd floor will be owners private storage. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             13) The 2nd floor rooms are classified as storage rooms.  
a) What will be stored inside the storage rooms? 
b) What does “NNO” in NNO Storage mean? 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: "Not Normally Occupied", "Low Hazard Storage". 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             14) Plans indicate a prep kitchen with warming ovens. NFPA 1:50 
a) Please verify there will be NO cooking conducted.  
b) Provide manufacturer spec sheets for ALL cooking equipment. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Confirmed the space is a PREP space, No cooking. Please see provided spec for warming equipment. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             15) I do not see any door hardware identified in the Door Schedule on Sheet A601. Also, not all doors are identified. For example, Fire Protection Closet interior and exterior doors, Door Tags: S1, E, 03B, 04B, 52A, also, the 2nd Floor doors are not identified. 101:12.2.2.2, 101:42.2.2.2 
a) Provide in the Door Schedule ALL doors including new, existing, swing type and roll up type doors. 
b) Provide door hardware information for each door, new and existing. 101:12.2.2.2.1 
c) Provide fire rating for doors that are fire rated. 
d) Identify the doors to have panic hardware installed. 101:12.2.2.2.3 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Please see A601 Revision 1 for updated hardware, egress information. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             16) Will there be any Special Locking Arrangements such as, but not limited to: Access Control, Mag-Locks, Delayed-Egress Electrical Locking Systems, Sensor-Release of Electrical Locking Systems, Door Hardware Release of Electrically Locked Egress Door Assemblies, Etc.? 
If Yes, Demonstrate compliance with the appropriate code section of 101:7.2.1.6 AND 101:12.2.2.2. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: None, per owners verification at in person meeting on 04/26/24. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             17) Sheet A101 provides tables and chairs along with row seating (non-fixed) on the same Sheet. The seating arrangements are intermingled and are imposed over each other. 101:2.5.11 
I cannot provide a review/approval for an approved seating Layout with the different types of seating imposed over each other. 
If you are looking to receive an approved seating layout, you will need to provide scaled seating layout meeting the provisions of 101:12.2.5 for each seating arrangement. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: See A801 and A802 Revision 1 drawing for 2 possible seating configurations. 
Thursday, June 20, 2024 1505 hrs. DF: I spoke with Architect Conner Dowling regarding the seating arrangements submitted. Due to time constraints and that there are a few outstanding comments to be addressed outside of the seating, we agreed to hold the seating review until the next resubmittal. 
----------------------------- 
Tuesday, July 30, 2024 DF: Reviewer's Response: No RTC Provided. Seating diagrams on Sheets A801 and A802 show the following. 
Sheet A801: Shows 8 seat Round tables in the main room fo0r a total seating of 248 Persons. The Sheet calls out "Seating Arrangement for 250".  
Sheet A802 : Shows non-secured seating in three (3) sections containing 204 chairs . There is a 375 SF Temp Platform/Stage at one end providing an occupant load of 25 persons (375÷15). A total occupant Load for this arrangement is 229 Occupants. 
Both Sheets A801 and A802 provide incorrect occupant load calculations. 
**Update the total occupant load counts on each sheet. 
Tuesday, July 30, 2024 1320 hrs. DF: Spoke with Architect Conner Dowling via phone. Conner agreed to place a HOLD 105 Revision to update the Sheets affected. 
                         | 
                            7/30/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             18) Provide electrical Sheets providing Emergency Lighting in compliance with 101:12.2.9 101:13.2.9 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Provided in Revision 1 drawings. 
Thursday, June 20, 2024 DF: Reviewers Response: Electrical Sheet does not show emergency lighting throughout the building. 
----------------------------- 
Tuesday, July 30, 2024 DF: RTC: Please see updated electrical lighting plan Sheet and cut sheets submitted REV 2. 
Tuesday, July 30, 2024 DF: Reviewer's Response: Sheet 150 shows combination emergency lighting identified in the Lighting Legend. Exit signs are identified by a typical exit sign symbol. I am able to identify some emergency lighting EL fixtures by the circles "E" with two triangles, however this symbol is not identified in the Lighting Legend.  
Based on the Lighting Legend and the circled "E" symbols the following areas need EL's or need additional EL's: Green Room, Groom Lounge, Lobby, RR Lounge, Bridal Lounge, Event Space, Loading 180, Fire Protection Room 190, Prep Area, and Back Hallway 155. 
Either Add emergency lighting to these areas or provide Emergency Lighting Photometrics demonstrating compliance with NFPA 101:7.9.2.1.1. 
Tuesday, July 30, 2024 1320 hrs. DF: Spoke with Architect Conner Dowling via phone. Conner agreed to place a HOLD 105 Revision to update the Sheets affected. 
                         | 
                            7/30/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             19) I am unable to verify the Normal Egress Lighting of the interior Stairs complies with the 10 foot-candles at the walking surface. 101:42.2.8 101:7.8.1.3(1) 
Provide Normal Egress Lighting demonstrating compliance with 101:7.8.1.3(1). 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: No work at existing stairs at level 2. Level 2 is owners personal storage. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             20) Provide additional Exit signage at the following location: 101:12.2.10 
·       Inside back Hallway adjacent to the doors to RR Lounge G160b 
·       Move the Exit sign in RR Lounge to middle of the opening of RR Lounge and Event Space 
·       Need Exit sign at exterior door G156 
No Exit Signs noted on 2nd floor. Provide Exit signs. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: See Revision1 G101 for added exist signage. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             21) Provide arrows with the EXIT signs to show direction of egress travel. 101:7.10.2 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Please see Sheet G101 Revision 1 for arrows. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             22) The following rooms are identified as Storage/Mechanical. Combustible material shall not be stored in boiler rooms, mechanical rooms, or electrical rooms. Exception: Materials and supplies for the operation and maintenance of the equipment shall be permitted. NFPA 1:10.19.5.1 
Storage/Mechanical Rooms: 113, 161, 178, 182 
Provide Signage stating NO STORAGE or, Separate the storage area from the Mechanical Area in accordance with Section 8.7 of NFPA 101. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Please see A101 for HVAC closets. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             23) Provide Separation of the Storage Rooms and Fire Protection Room in accordance with Section 8.7 of NFPA 101. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Fire Protection Room is now adjacent to "office" per Revision 1. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             24) Will there be any Fuel Burning (Wood, Natural or Liquid Propane, etc.) appliances, Mechanical Equipment, etc.? 101:12.3.4.4 
If Yes, Demonstrate compliance with 101:12.3.4.4. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: None, per owners verification at in person meeting on 4/24/24. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             25) Provide a Risk Analysis for Mass Notification Systems in accordance with Section 9.14 of NFPA 101. 101:12.3.4.5 
Provide the Risk Analysis for review. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Contractor to provide and coordinate. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             26) Vertical Opening in the interior Stairway and 2nd Floor corridor. 101:42.3.1 
Demonstrate how you will comply with 101:42.3.1 and Section 8.6 of NFPA 101. 
----------------------------- 
Wednesday, June 19, 2024 DF: RTC: Per NFPA 101:43.4.7.1 the stairway is not required to be enclosed. 
Thursday, June 20, 2024 DF: Reviewer's Response: Spoke with Architect Conner Dowling via phone regarding the classification of this building as Historical. After discussion, Mr. Dowling stated that he is going to classify this building as Historical with work falling under NFPA Chapter 43.10.1(2) which will utilize Sections 43.3, 43.4, 43.5, 43.6, and 43.7 as they relate according to 101:43.10.1(2). 
Based on this information and per 101:42.3.1(2) the existing open stairs is permitted. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             INFORMATIONAL ONLY NO RESPONSE NECESSARY:
 
  
ASSEMBLY Occupancy: 
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet: 
Wall and ceiling finish: Corridor, Lobbies: Class A or B, and Class A in Enclosed Stairways. 101:12.3.3.2 
Assembly Areas: Wall and ceiling finish will meet Class A or B in areas with Occupant Loads greater than 300, and A, B or C in areas with Occupant Loads Less than 300. 101:3.3.3 
Floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non-carpet flooring. 101:12.3.3.5. 
Floor Finish in Exit Enclosures and exit access corridors and in spaces not separated from them; not less than Class II. 101:12.3.3.5.2 
STORAGE Occupancy: 
Interior wall and ceiling: Class A, B or C. 101:42.3.3.2 
  
Interior Floor Finish in Exit enclosures and in exit access corridors shall be Class I or II. 101:42.3.3.3.1 
NOTE: If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             INFORMATIONAL ONLY NO RESPONSE NECESSARY: Air handlers with more than 2000 CFM are required to have duct smoke detectors. NOTE: If there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. 90A:6.4 Where smoke detectors required by 6.4 are installed in a building not equipped with an approved fire alarm system as specified by 6.4.4.2, the following shall occur: 1. Smoke detector activation required by section 6.4 shall cause a visual signal and an audible signal at a normally occupied area.  2. Detector troubles shall be indicated visually or audibly in a normally occupied area identified as air duct</spa 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             INFORMATIONAL ONLY NO RESPONSE NECESSARY: Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following:  NFPA 101 7.9.2.3 (1) Failure of a public utility or other outside electrical power supply (2) Opening of a circuit breaker or fuse (3) Manual act(s), including accidental opening of a switch controlling normal lighting facilities. NOTE: Our office has experienced issues with large projects that have emergency generators not being prepared to comply with item #2.  
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             INFORMATIONAL ONLY NO RESPONSE NECESSARY: Buildings containing Fire Alarm Systems, Fire Sprinkler Systems, etc. and/or Security Systems that make it difficult to access the building in an emergency are required to have a Fail-Safe box. NFPA 1:18.2.2.1
  
Please contact St Johns County Fire Rescue Secretary Dawn Lyons at 904-209-1712 for the correct order form. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             INFORMATIONAL ONLY NO RESPONSE NECESSARY: 101:8.3.2.4 Each new Fire Wall, Fire Barrier, Fire Partition, Smoke Barrier, Smoke Partition, or any other new wall required to have protected openings shall be permanently identified with signs or stenciling above any decorative ceiling and in concealed spaces, with the wording “FIRE AND SMOKE BARRIER – PROTECT ALL OPENINGS”, or similar language. Such signs or stenciling shall be 4 in. high letters, ½ in. stroke, and not more than 15 ft. on center. 
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual. 
A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
  - Fire Alarm System - Fire Sprinkler System  - Fire underground - Fire/Smoke Damper Test/Inspections - In-Building Radio Enhancement System (BDA) TEST / PERMIT - HOLD 105 INSP - Revision to address comments #9, 17, and 18. -  -  -  -  -  -  
                         | 
                            6/20/2024
                         | dfeagle | 
		 
			| 
                            
                         | 
                             27) Thursday, June 20, 2024 DF: New comment based on review of 1st Resubmittal: Exit signs must match BOTH Electrical page(s) and Life Safety Code page(s). The Electrical Sheet does not show any Exit Signs. The Electrical Sheet is the Sheet the Electrician installs the Exit Signs From. 
Update the Electrical Sheet. 
                         | 
                            7/30/2024
                         | dfeagle | 
		 
	 
 
     
                                     | 
                                 
                             
                         |