Plan reviewed for the fire underground supplying the sprinkler system for a 2 story 33,660 SF shell buildings. This underground was submitted with the Fire sprinkler which was submitted originally 7/18/24, resubmitted on 3/28/25 and approved on 7/21/25.
The parking lot was adjusted causing a slight move of the underground but did not change the position of the hydrant or the FDC. This change was addressed with MODCP 25-114.
The underground is supplied from a 12" x 8" sleeve and gate valve.
The 8" DR-18 PVC is reduced using an 8"x 6" reducer
6" DCDA insulated Backflow that is electronically supervised.
6" Private (red) FH with Gate valve located at 6"x6" x 4" tee
4" Dr 18 PVC and gate valve supplies the 4" supply and continues to the 4" riser and finishes 1' AFF
A free standing insulated 4" FDC with wafer check and 5" storz with 30 degree downturn.
Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: J.L. Hatcher 904-209-1741, jlhatcher@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.