SJC Home
Clearance Sheet C2023-001811

 Department IssuesSigned OffIntl

 Plans for a 33,659sf 2 story shell building that is indicated to be a daycare and an office building, separated by a 2 hour tenant separation wall.  The single story side is 13,434sf, the 2 story side is 10,098sf on both floors.  The building will have a fire sprinkler and a fire alarm system, and is constructed as type IIB.  NO restrooms are indicated but a slab is proposed.   The plan was submitted and reviewed as business.   


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

Resubmittal Reviewer: 
Aaron (Bryan) Connell 904-209-1778 aconnell@sjcfl.us 
12/8/2023- ABC: 1st Resubmittal  reviewed

12/8/2023 aConnell

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 7th Ed.

 

12/8/2023- ABC: Response to comments submitted.

12/8/2023 aConnell

1) An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided.  It is not a full set of shop drawing  FLORIDA ADMINISTRATIVE CODE 61G15-32.004

12/8/2023- ABC: Response: "Contractor including these documents with this submittal"

**Noted FS-1 thru FS-4 was added to plan set.

12/8/2023 aConnell

2) Clarify what is being installed as part of this shell.   The electrical plan clearly indicates dark shaded walls and the central corridor.  The life safety plan indicates very faint, the walls and corridor.  Are the walls and corridor on the second plan part of this permit?  If yes, darken them.  If not, indicate this on all plans or remove.

12/8/2023- ABC: Response: "2nd floor layout is conceptual design only. Actual design will be submitted wit build out plans. Please see scope of work note on Sheet T1.0 Rev.1."

**Note is located on Sheet T1.0

12/8/2023 aConnell

3) Related to comment 2, what is the design intent for egress from the second floor.  The second floor stair is not indicated to be enclosed currently.  Is the intent to have a 1 hour rated corridor connect the rated stair across to the outside door leading to the outside stair essentially considering the entire corridor as an exit enclosure or exit passageway leading to the exits?  If yes this must all be indicated and installed now as part of the shell.  If not, the stair will need to be fully enclosed with a rated enclosure and rated door, because the common path cannot be met from the second floor if the interior stair is not fully enclosed becoming an exit access stair.  It would need to be an exit which is required to be enclosed (rated).  NFPA 101:38.2.4.1, 38.2.4.2. and 7.2.2.5.1.1 Clarify and demonstrate your design intent.

12/8/2023- ABC: Response: "Floor plan layout has been revised at the elevator and stair area to show separate foyer and elevator lobby. Please see sheets LS1.0, LS2.0, A1.0, A1.2, A1.4C,A1.5D, A3.0, M1.0 on Rev.1"  

12/8/2023 aConnell

4) Regardless of how the second floor egress is intended per comments 2 and 3, elevators are not permitted in exit enclosures.  NFPA 101:7.1.3.2.

12/8/2023- ABC: Response: "Floor plan layout has been revised at the elevator and stair area to show separate foyer and elevator lobby. Please see sheets LS1.0, LS2.0, A1.0, A1.2, A1.4C,A1.5D, A3.0, M1.0 on Rev.1"     

12/8/2023 aConnell

5) I am unable to see the plan details such as notes, callouts, labels etc. at the 1/16th scale provided.   Provide a minimum of a 1/8th scale for review of the LS plans, floor plans, elevations and details. 

12/8/2023- ABC: Noted plan scale has been revised to 1/8 scale. 

12/8/2023 aConnell

6) Is the single emergency light fixture indicated enough to illuminate the entire exterior stair run?

12/8/2023- ABC: Noted additional emergency lighting fixture has been added to the exterior stairs.

12/8/2023 aConnell

7) Regarding comment 3, if the corridor is constructed, additional emergency lighting will be required.

12/8/2023- ABC: Response: "The 2nd floor layout is conceptual design only. Actual design will be submitted wit build out plans. Please see scope of work note on Sheet T1.0 Rev.1."

**Note is located on Sheet T1.0

12/8/2023 aConnell

8) It appears that the storage room under the stairs is accessed from within the stair enclosure, or future stair enclosure.  This is not permitted per NFPA 101:7.2.2.2.5.3.2 which is a Florida Addition.  Provide a detail demonstrating compliance with all 3 parts of this section for the storage area.

12/8/2023- ABC: Response: "Door to this space was moved from the elevator foyer to inside tenant space. Space under the stair to be protected by fire rated ceiling assembly UL D502; see sheets LS1.0, A1.0, A1.5C, A1.5D, A3.0 on Rev.1."

12/8/2023 aConnell

9) Sheet T1.0 under "scope of work" note 4 indicates new 2 hour tenant separation. LS1.0 indicates a 1 hour wall.  Ensure that they match.

12/8/2023- ABC: Response: "A 2 hr separation is required for not sprinklered; in this case the building is sprinklered and only 1 hr is required. This has been clarified on revised sheet T1.0 on Rev.1."   

12/8/2023 aConnell

10) This building is required to have a third party contractor conduct a two-way radio communication test in accordance with NFPA 1:11.10 and NFPA 1225 (2022 ED.) before the 105 framing inspection. St Johns County Fire Rescue’s radio control frequency is 853.8875.

-If it passes the inspection radio testing, you will need to submit a copy of the testing results as a revision so we can record the documentation and remove the hold.

- If the third party paperwork indicates the test is not satisfactory, then the contractor will have to submit for a revision. The revision will need to include: the unsatisfactory test paperwork, outline of corrective measures, and plans to illustrate the corrective measures to meet requirements provided by the design professional.

At the final, you will be required to provide satisfactory testing by the third party contractor following the installation of the in building radio enhancement system.

12/8/2023-ABC: Response: "Acknowledged"

12/8/2023 aConnell

11) Informational

The fire sprinkler system is required to be electronically supervised, which includes all valves including the backflow preventer.  This will be verified when sprinkler and fire alarm shop drawings are submitted.

12/8/2023- ABC: Response: "Acknowledged"   

12/8/2023 aConnell

12) INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- Fire alarm system
- Fire sprinkler system
- Fire underground
- In-Building Radio Enhancement System (BDA) TEST / PERMIT

12/8/2023 aConnell