Plan reviewed for revision to building plans to include FA page for generator monitoring.


Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: S. Schnellenberger 904-209-1778, SSchnellenberger@SJCFL.US

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

5/16/2024 sschnellenberger

1. The Emergency Generator shall be monitored by the Fire Alarm System for a) Generator Running, b) Generator Fault, and c) Generator Switch in Nonautomatic Position. 101:9.1.3.2