| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for New BDA system: BDA: HONBDA-D-7S27B, Remote Annunciator: ???, Backup Battery System: HONBDA-BTTY-100100
Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
| |
|
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the permit center. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8". - Code responses shall reference Florida Fire Prevention Code, 7th Ed.
|
| |
|
|
1) Provide the Code Summary identifying the Florida Fire Prevention Code 8th Edition and NFPA 1225 2022 Edition.
Verify the plans have been designed to these code and standards.
|
| |
|
|
2) Provide the St Johns County Fire radio frequencies list on the plans.
|
| |
|
|
3) Demonstrate on the plans the Signal Strength and Quality with the BDA system. 1225:18.9
|
| |
|
|
4) Show the location of the Dedicated Annunciation panel in the 1st Floor Lobby adjacent to the FACP/FACP Remote Annunciator.
|
| |
|
|
5) (1225:8.14.2, 1225:18.4.2.2) Show the location of the Dedicated Annunciation panel in the 1st Floor Lobby adjacent to the FACP/FACP Remote Annunciator. The Dedicated Annunciator shall provide visual and labeled indications of the following for each system and RF-emitting device:
1) Normal ac power
2) Loss of normal ac power
3) Battery charger failure
4) Low-battery capacity (i.e., to 70 percent depletion)
5) Signal source malfunction
6) Active RF-emitting device malfunction
7)Active system component malfunction
|
| |
|
|
6) Provide Color Heat Maps demonstrating the system will be in compliance with 1225:18.8.
|
| |