Plan reviewed for New NFPA 110 Type 1, Level 10, Class X (128 hr.) Outdoor Emergency Power Generator: Generac SD400, 400 kW Diesel Generator, Fuel Tank: 3,550 Gallons - 90% usable capacity, 4,033 Gallons 100% capacity. Run Time 96 hrs. + 33% (128 Hrs.)
Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.