SJC Home
Clearance Sheet C2023-000817

 Department IssuesSigned OffIntl

Plan reviewed for new underground fire main system beginning at isolation valve from 6" ZURN Wilkins RPDA, 117 LF of 6" PVC DR-18 to 6" Hydrant Tee then continuing 133 LF to 1' AFF termination. Free Standing 5" STORZ with 30° Down Angle FDC connected to a 6" PVC DR-18 to 1' AFF Termination.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 7th Ed.

 

1) Plans include Shop Drawings (Sheets 1 and 2), Civil Utility Drawings (C-1, C-2, C-3, C-10, C-11, C-14, C-15, C-16), Domestic Plumbing Sheets (P001, P002 (Med Gas), P101) and Fire Protection Sheets - Aboveground Sprinkler System (FP001, FP100, FP200)

Some of the Civil Drawings conflict with the Shop Drawings (i.e. RPDA vs DCDA BFP).

a) Remove the Civil Drawings, Domestic Plumbing, Med Gas (requires separate permitting)and the above ground Sprinkler Plan Sheets (Sprinkler Plan already submitted) that do not apply and/or conflict.

 

1) What method will you use to prevent Freezing of the BFP and the FDC? 24:12.2.3

Provide the manufacturer's spec sheets.

 

2) What method will you use to prevent corrosion? 24:10.6.2.5

Provide the manufacturer's spec sheets.