SJC Home
Clearance Sheet C2023-000390

 Department IssuesSigned OffIntl

Plans for a revision from the previously approved sheet FP1 of 2 to add sprinkler coverage in the restrooms and the fire sprinkler riser room that were added in a previous building plan revision.  The original building plan revision to add the walls and the restrooms does not indicate a riser room, which blocks a marked egress door.  A hold is being added to the permit and a building plan revision is required to add the riser room.   


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

9/23/2022 PWebb