Clearance Sheet C2022-004022

 Department IssuesSigned OffIntl

Plan reviewed for New BDA System: Honeywell BDA-1-L1, Remote Annunciator: Honeywell BDAANN MSC1-L1, 4 omni-directional antennas, Roof antenna, etc.

Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

-----------------------

Friday, April 12, 2024 DF: Review of 1st Resubmittal.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.

 

1) Provide Battery Calc's.

-----------------------

Friday, April 12, 2024 DF: Provided.

4/12/2024 dfeagle

2) Provide Color Heat Map(s).

-----------------------

Friday, April 12, 2024 DF: RTC: Two (2) copies of heat map provided by FIPLEX by Honeywell design team.

-----------------------

Friday, April 12, 2024 DF: Reviewer's Response: The heat map shows a distorted color block around each antenna. However, the heat map does not include the entire building demonstrating coverage. It appears that there may have been a printing issue.

Provide an updated heat map covering the building.

 

3) Provide on the plans: Frequencies installed/test to.

-----------------------

Friday, April 12, 2024 DF: At the time of survey, channel 853.8875 was active. The following channels were also tested: 853.7125, 853.6375, and 853.3875. The BDA provided is a twenty-channel unit. If the County provides us with active channels they want amplifier, we will program them into the unit.

Friday, April 12, 2024 DF: Reviewer's Response: Plans have not been updated to show on the plans, the Control Channels 853.8875 (Primary), 853.7125, 853.6375, and 853.3875. Show these channels on the plans.

 

4) Demonstrate on the plans compliance with 1225:18.14.1 (Fire Alarm System Monitoring) and 1225:18.14.2 (Dedicated Annunciation).

-----------------------

Friday, April 12, 2024 DF: RTC: Two (2) copies of amended fire alarm matrix showing interconnect from BDA to the fire alarm are attached.

 

4/12/2024 dfeagle