SJC Home
Clearance Sheet C2022-004019

 Department IssuesSigned OffIntl

Plan reviewed for a new Fire Alarm System monitoring the building's Sprinkler System, BFP, and all of the sprinkler system control valves. FACP is a Fire-Lite ES-50X Intelligent Addressable. FACP is located in the Electrical Room with exterior access.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit. All plan pages must be the same size.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

 

1) The buildings Sprinkler System does not show the BFP being electronically supervised. SJCFMO, 101:9.7.2

---------------------------

Friday, March 3, 2023 1040 hrs. DF: I spoke with Mr. Shawn VanHorn via phone regarding the BFP Supervision. I agreed to hold the plans until Wednesday (02/08/2023) COB for the updated plan sheet to be delivered.