Plan reviewed for New Wet Sprinkler system with 1,829 Sprinkler Heads, A Electrically Driven Peerless 1,500 GPM Centrifugal Fire Pump, Firetrol FTA1000 Fire Pump Controller, Firetrol Jockey Controller, 6 Port CLA-VAL wall mounted Test Header.
Sprinkler System is connected to the 10" underground Fire Main ~ 1' AFF, reduced to 8" Steel pipe to Fire pump and then to the riser manifold containing 4 8" System Risers. System 01 covering 41,813 SF with 450 heads, System 02 covering 41,287 SF with 450 heads, System 03 covering 41,860 Sf with 450 heads and System 04 covering 42,707 SF with 475 heads.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.