Plan reviewed for Non-sprinkled 3215 sf Class B mercantile occupancy interior renovation. Reviewed using FFPC 7th edition effective Dec. 31, 2020.

Reviewer: 
Anthony Gedris 904-209-1741
Aaron Connell


To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

2/10/2022 aConnell

**INFORMATIONAL ONLY NO RESPONSE NECESSARY:
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- Wall and ceiling finish will meet Class A, B or C. 101:36.3.3.2

- Floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non-carpet flooring. 101:36.3.3.3

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

2/10/2022 aConnell

INFORMATIONAL ONLY NO RESPONSE NECESSARY:

Class A and Class B mercantile occupancies and mall structures shall have emergency lighting facilities in accordance with Section 7.9.   NFPA 101:36.2.9 Emergency Lighting.

Verify that the existing emergency and exit lighting circuit is tied to the lighting circuit for the area served.  This will be verified at final.