Plan submitted for new Ansul r102 system protecting an 11' hood with 11 flow points avail and 8 used. Cooking equipment L to R: Vulcan 60x24 griddle, Vulcan 12x24 2 eye, Vulcan oven. Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

10/26/2022 VVitori

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

10/26/2022 VVitori

1) Plan shows duct is 18" and is protected using a 1W nozzle. Looking at page 4-1 of manual, the 1W only covers ducts up to 50" perimeter. Either clarify duct size or update nozzle type used.

Wednesday, October 26, 2022 No response to comments provided. Plans now show duct is 16" diameter.

10/26/2022 VVitori

2) This suppression submittal was submitted under the SHELL building and not a suite with a build out. Upon resubmitting, resubmit under appropriate suite number/clearance sheet.

10/26/2022 VVitori