2- I see a spec sheet within the submitted spec sheet packet for an FDC, but I do not see anything within the scope of work. Please clarify if an FDC is going to be within the scope of work. If so, it will need to meet the following criteria:
FDC connections shall be equipped with a five (5) inch Storz connection and shall have a 30 degree downward deflection.
This applies to all FDC’s regardless being on a building or free standing.
NFPA 24:5.9.1.2, and 5.9.2.4