Clearance Sheet C2021-008928

 Department IssuesSigned OffIntl

KT Carter Contracting, Ray Gauvin 354-9999

Plan APPROVED. Scope of work is removing 6" cap and installing gate valve to isolate sprinkler line, extend 6" DR-14 approx. 30' to finish 1' above finished floor. 

**Fire plan reviewer-make sure check valve in fire sprinkler riser.**

2/15/2022 SMurray

FDC to be on building.

**Per Fire Inspector Supervisor, a two 2 1/2" FDC allowed for this existing complex.** 

2/15/2022 SMurray

The following will be checked during fire inspections:

- Top of the pipe shall be buried not less than 2 1/2 ft to prevent mechanical damage (NFPA 24:10.4.2.2.2)
- Pipe under driveways shall be buried at a minimum depth of 3 ft (NFPA 24:10.4.2.2.3)

2/15/2022 SMurray