| | Department Issues | Signed Off | Intl |
|
|
Plan submitted for new 6570sf construction type VB sprinklered (with fire alarm) shell to be a mercantile. Reviewed using FFPC 7th edition effective January 1, 2021.
Reviewer: V.Vitori 904 209 1748
To schedule fire inspections call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
1/4/2022
| VVitori |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
1/4/2022
| VVitori |
|
|
1) This is a preliminary review. Do not resubmit until clearance sheet obtained.
NOTE: Based on fire's site review, additional comments may be provided.
|
1/4/2022
| VVitori |
|
|
2) How will sprinkler riser room be kept above freezing? NFPA 13
Tuesday, January 4, 2022 Response to comment indicates "An Electric Heater w/thermostat is provided in the sprinkler riser room. See sheet E1.1 for the Electric Heater Specifications. The house panel H provides the circuit (#14) for the heater on Sheet E2.1."
|
1/4/2022
| VVitori |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until a permit has been pulled : - Fire alarm system - Fire sprinkler system - Fire underground
|
1/4/2022
| VVitori |