Plans for a revision to identify all of the special locking arrangements for the building. Life Safety sheets and technology sheets have been provided along with accompanying 087100 specifications with details for each hardware group. It is important to note that allowances of NFPA 101:18.2.2.4 (1), 18.2.2.5, 18.2.2.5.1, and 18.2.2.5.2 were not utilized. There are no patients that require specialized security measures (Psych units, Alzheimer/dementia units etc.) or special protective measures (Ped units, maternity units). There is 1 sensor release door (1300.8) and the remaining are either delayed egress, or released mechanically with fire exit hardware.
Reviewed using FFPC 8th edition effective Dec. 31, 2023.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.