Plan reviewed for the installation of a new Clean agent (FK-5-1-12) extinguishing system on the 2nd floor Tec Room of the Flagler Health Durbin Park Hospital.
The Clean agent control panel to also control the pre action valve in the room.
Battery Calcs provided 2 12v-12ah
1- 72" AFF to top Model FC(22 Clean Agent Releasing Panel (CARP)
1- Agent releasing strobe wall mounted 80" AFF to bottom of lens
1- Second Alarm Horn/Strobe wall mounted 80" AFFF to bottom of lens
1- Manual Release pull Station
1- 24 Volt Motor Bell Siemens
1- Control Relay
1- Monitor Module
2- Addressable Control Point
1- Pressure switch-Alarm
1- Abort Station
1- Low pressure switch supervisory
1- Agent Releasing solenoid
1- 120V Surge protector
2- Dual Monitor Module
2- Mini monitor Module
1- Monitor module
4-- Multi Criteria Ceiling mount Model OOH941 Siemens Smoke detectors
2- 360 Degree Gas Discharge Nozzle Siemens
Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: J.L. Hatcher 904-209-1741, jlhatcher@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.