Clearance Sheet C2021-008654

 Department IssuesSigned OffIntl

Plan reviewed for the installation of a pre-action fire alarm. The pre action FACU to be monitored by the main building fire alarm.

Battery Calcs provided 2 12v-12ah

 1- 72" AFF to top Model FC922 Siemens Fire Alarm Control Unit 

 1- Supervisory Low pressure switch

 1- Alarm pressure switch

 1- Supervisory Tamper switch

 1- Releasing solenoid

 1- 120V Surge protector

 2- Dual monitor Module

 6- Ceiling mount Model OOH941 Siemens Smoke detectors

 3- 48" AFF Model XMS-D Manual Pull station

Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: J.L. Hatcher 904-209-1741, jlhatcher@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

12/17/2025 jlhatcher