SJC Home
Clearance Sheet C2021-008654

 Department IssuesSigned OffIntl

Plans for a revision to the following sheets: S201, S207, S208, S210, S401, S402, S901, G001, G100, AS204, AS205, AS206, AS206ACS, A251, A350, A353, A401, A402, A403, A404, A405, A406, A452, A453, A454, A730, A731, A734, A900CS, G002, G030 AL201, AL202, AL203, AL204, AL206, A201, A201A1, A201A2, A201B1, A201B2, A202, A202A1, A202A2, A202B1, A202B2, A203, A203A1, A203A2, A203B1, A203B2, A2040, A2041, A2042, A2050, A2051, A2052, A2060, A2061, A482, A502, A504, A505, A506, A507, A508, A509, A510, A511, A512, A513, A514, A515, A516, A517, A518, A519, A520, A521, A522, A523, A524, A26, A527, A528, A529, A532, A535, A536, A537, A538, A539, A540, A541, A542, A543, A545, A546, A547, A548, A550, A551, A552, A560, A561, A562, A563, A564, A565, A566, A567, A568, A569, A570, A571, A581, A582, A585, A586, A587, A588, A594, A595, A601A, A601B, A602A, A602B, A603A, A603B, A604AB, A605AB, A610, A611, A612, A613, A651, A807, A819, A834, A900, A901, A902, A903, A904, A905, A950, I001, I007, I008, I201A1, I201A2, I201A3, I201B1, I201B3, I201A1, I202A3, I202B1, I202B2, I202B3, I203A3, I203B1, I203B2, I203B3, I2041, I2042, I2043, I2051, I2052, I2053, FP001, FP201A, FP201B, FP201C, FP202A, FP202B, FP203A, FP203B, FP204, FP205, P002, P101A, P101B, P101C, P102A, P102B, P103A, P103B, P104A, P104B, P105, P201A, P201B, P202A, P202B, P203B, P204, P301A, P302A, P401, (MC101, MC102, MC303 NOT PROVIDED) M001, M002, M003, M004, M007, M201A, M201B, M202A, M202B, M203A, M205, M211A, M211B, M212A, M212B, M401, M601, M605, M606, E001, E002, E004, E006, E007, E008, E009, E010, E011, E013, E100, E101, E101A, E101B, E101C, E102A, E102B, E103A, E103B, E104, E105, E106, E201A, E201B, E202A, E202B, E203A, E203B, E204, E205, E301, E301A, E302, E302A, E302B, E303, E303A, E303B, E304, E304A, E401, E402, E403, E404, E405, E406, E409, E502, E504, E505, E512, E513, E514, E516, E517, E519, E521, E522, E524, E601, E603, E604, E701, T100A, T100B, T101A, T101B, T102A, T102B, T103A, T103B, T104A, T105A, T201A, T201B, T202A, T202B, T203A, T203B, T204, T205, T501, T502, and T706.

A detailed revision narrative has been provided.  One notable change is the standpipes have been changed to manual wet in the FP plans. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

8/26/2025 PWebb

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.

8/26/2025 PWebb

1) Doors 2307, 2316, 2400B, 3244, 3258, 3112, 3113, 3127, 3225, 3123, 3109.1A, 4203, 4215A, 4215B, 4226, 4224, 4222, 4233, 5145A, 5145B, 5133, 5123, 5127, 5211, 5203, 5215A, 5215B, 5226, and 522 indicate the addition of a card reader.  How will this be achieved while maintaining egress?  This should be clarified when the updated 087100 specs are provided per a later comment.

------------------------

Tuesday, August 26, 2025 PJW- Not addressed on the response to comments.  No 087100 specifications provided. 

-----------------------

Tuesday, November 4, 2025 PJW- 087100 provided. 

11/4/2025 PWebb

2) Sheet E101B

The revision indicates removing all lighting from the walk in cooler and freezer.  This is not permitted.  Normal lighting is required per NFPA 101:18.2.8, 7.8. 

------------------

Tuesday, August 26, 2025 PJW- Per RTC, "Please reference sheet E101B, which shows lighting for the cooler and the freezer (Provided as part of the equipment).

Tuesday, August 26, 2025 PJW Reviewer-  E101B provided on separate sheets. 

8/26/2025 PWebb

3) Sheets MC101, MC102, and MC103 are indicated in the revision narrative, but the plan sheets were not provided.  Provide the sheets or correct the revision narrative.

--------------

Tuesday, August 26, 2025 PJW- Per RTC, "The reference to these sheets has been removed." 

Tuesday, August 26, 2025 PJW Reviewer Response- The revision narrative has not been changed or modified.  It still contains the above sheets. 

-----------------

Tuesday, November 4, 2025 PJW- I spoke to Brian Schulz, Senior Architect, he indicated that the MC plans referenced above are for the CEP building that was reviewed under separate cover. 

11/4/2025 PWebb

4) For sheets S201, S207, S208, S210, S401, S402, and S901 the revision narrative is labeled as "structural volume 1".  The plans indicate volume 3 in the lower right corner of the sheets.  Make the necessary corrections.

----------------

Tuesday, August 26, 2025 PJW- Per RTC, "The revised sheets have been provided with this response.  The title block has been corrected to "Volume 1"" 

8/26/2025 PWebb

5) The revision narrative includes several project manual specifications as part of the revision.  Provide them for review or remove them from the revision narrative. 

-------------------

Tuesday, August 26, 2025 PJW- No project manual provided.  Provide the manual or remove the references to the manual from the revision narrative. 

-----------------

Tuesday, November 4, 2025 PJW- Information provided. 

11/4/2025 PWebb