Clearance Sheet C2021-008654

 Department IssuesSigned OffIntl

Plans for the installation of a BDA/DAS for a 6 story hospital using a ADRF system.  Reviewed using NFPA 1225. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.

 

1) The specifications for the PSR-78-8527-PKG Repeater do not indicate that the product meets UL 2524 as required by NFPA 1225:18.12.1.3.  Unable to find on the website.    

 

2) The specification sheets for the Repeater (PSR-78-8527-PKG) does not indicate Nema 4 or 4X compliance.  NFPA 1225:18.3.1.2.   

 

3) The battery backup (ADRF-BBL-X) specification sheets do not indicate compliance with NEMA 3R per NFPA 1225:18.3.1.1.  Unable to find on the website.