Clearance Sheet C2021-008654

 Department IssuesSigned OffIntl

Plans for a large revision to a hospital for the following sheets:

G001, S001, 2101, S201, S201A, S2O1B, S201C, S202, S202A, S202B, S203, S203A, S203B, S204, S204A, S204B, S205, S205A, S205B, S206, S206A, S206B, S207, S208, S209, S210, S301, S302, S303, S304, S305, S306, S401, S402, S403, S501, S601, S603, S701, S702, S703, S801, S901, AS201, AS202, AS203, AS204, AS205, AS206, AS207, G100, A201CS, A201ACS, A201BCS, A201CCS, A201CS, A202CS, A202ACS, A202BCS, A203CS, A203ACS, A203BCS, A204CS, A204ACS, A204BCS, A205CS, A205ACS, A206CS, A206ACS, A207CS, A207ACS, A207BCS, A250CS, A251CS, A252CS, A253CS, A300, A301, A302, A310, A311, A312, A313, A314, A320, A321, A350, A351, A352, A353, A400, A401, A402, A403, A404, A405, A406, A407, A408, A450, A451, A452, A453, A454, A701, A702, A703, A720, A721, A722, A723, A724, A725, A730, A731, A732, A900CS, G002, G010, G020, GO30, AL201, AL202, AL203, AL204, AL206, A201, A201A1, A201A2, A201B1, A201B2, A202, A202A1, A202A2, A202B1, A202B2, A203, A201A1, A203A2, A203B1, A203B2, A2040, A2041, A2042, A2050, A2051, A2052, A2061, A480, A481, A482, A500, A501, A502, A503, A504, A505, A506, A507, A508, A509, A510, A511, A512, A513, A514, A515, A516, A517, A518, A519, A520, A521, A522, A523, A524, A525, A526, A527, A528, A529, A530, A531, A532, A535, A536, A537, A538, A539, A540, A541, A542, A543, A545, A546, a547, A548, A549, A550, A551, A552, A560, A561, a562, A563, A564, A565, A566, A567, A568, A569, A570, A571, A581, A582, A585, A586, A587, A588, A591, A592, A593, A594, A595, A596, A601A, A601B, A602A, A602B, A603A, A603B, A604AB, A605AB, a606AB, A610, A611, A612, A613, A650, A651, A652, A653, A654, A801, A802, A804, A805, A806, A807, A819, A900, A901, A902, A903, A904, A905, A950, A951, I000, I001, I007, I008, I201A1, I201A2, I201A3, I201B1, I201B2, I201B3, I202A1, I202A2, I202A3, I202B1, I202B2, I202B3, I203A1, I203A2, I203A3, I203B1, I203B2, I203B3, I2041, I2042, I2043, I2051, I2052, I2053, I2061, G003, FP100, FP201B, FP201C, FP202A, FP202B, FP203A, FP203B, FP204, FP205, FP206, P002, P002, P100, P101A, P101B, P101C, P102A, P102B, P103A, P103B, P104A, P104B, P105, P106, P201A, P201B, P202A, P202B, P203A, P203B, P204, P205, P301A, P302A, P303A, P303B, P304, P305, P307, P401, P504, P601, P602, P603, P604, P605, P606, P607, P608, P609, P610, P611, P612, P613, P614, P615, P616, P617, P618, P619, M001, MOO2, m003, M004, M005, M007, M008, M009, M201A, M201B, M202A, M202B, M203A, M203B, M204, M205, M206, M211A, M211B, M212A, M212B, M213A, M213B, M214, M215, M216, M401, M402, M503, M504, M601, M602, M603, M605, M606, E001, E002, E004, E005, E006, E007, E008, E009, E010, E011, E012, E100, E101, E101A, E101B, E101C, E102A, E102B, E103A, E103B, E104, E105, E106, E201A, E201B, E201C, E202A, E202B, E203A, E203B, E204, E205, E206, E301A, E301B, E302, E302A, E302B, E303, E303A, E303B, E304, E304A, E305, E306A, E401, E402, E403, E404, E405, E406, E407, E408, E502, E503, E504, E505, E506, E507, E508, E509, E510, E511, E512, E513, E514, E515, E516, E517, E518, E519, E520, E521, E522, E523, E524, E602, E604, E701, T001, T002, T100, T101, T101A, T101B, T102, T102A, T102B, T103, T103A, T103B, T104, T104A, T105, T105A, T201A, T201B, T202A, T202B, T203A, T203B, T204, T205, T206, T501, T502, T601, T602, T603, T603.1, T604, T605, T606, T607, T701, T701.1, T702, T705, and T706.

A detailed itemized revision narrative was provided with the changes.  The changes include a change to the layouts of the 3rd and 4th floors. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.

 

1) Sheet FP201A is indicated in the revision narrative, but was not included in the plan-set. Provide the sheet or adjust the narrative.  

The following sheets have been provided in the plan-set but have not been included in the revision narrative: IA006, A831, A832, A833, and A834.  Remove the sheets, or include them in the narrative. 

 

2) Sheet AL203

The new 3rd floor meeting rooms are considered assembly occupancies per NFPA 101:18.1.3.10.  The plans identifies them as accessory occupancies.  However assemblies are not considered accessory occupancies in the fire code (NFPA 101:6.1.14.1.4) nor are they considered incidental occupancies (NFPA 101:6.1.14.1.3).  Therefore the 3rd floor in its entirety is being reviewed as Multiple/Mixed use, Healthcare and Assembly.  NFPA 101:6.1.14.3. 

Provide a code analysis based on both occupancy chapters and update the code summary to indicate this.   

 

3) Provide occupant load calculations on the plans for the meeting rooms utilizing both the concentrated (7) and unconcentrated (15) factors based on the potential flexible use of the space and what appears to be storage for the table and chairs. NFPA 101:7.3.1.2.  

 

4) It appears that the occupant load for both meeting rooms (room divider closed) will exceed 50 persons.  Based on this a second remote means of egress is required from both meeting room 3105B AND 3109A (room divider closed).  NFPA 101:12.2.4.2, 7.4.1.1. 

 

5) Door 3109B must swing in the direction of egress.  NFPA 101:7.2.1.4.2(1)  

 

6) Ensure that all doors leading from Meeting Rooms 3109B and 3109A are equipped with panic hardware.  NFPA 101:12.2.2.2.3. 

 

7) The occupant load for the 6th floor penthouse exceeds the 200' maximum permitted by NFPA 101:18.2.6.2.1.  This appears due to the removal of a wall rating. 

2/4/2025 PWebb

8)Informational comment

The question was raised regarding the door swing of electrical room 1279 since the door swing was changed from an out-swinging door to a in-swinging door.  Per the Architect, the room does not meet the ampere/voltage requirements that would require panic hardware.