SJC Home
Clearance Sheet C2021-008654

 Department IssuesSigned OffIntl
Informational

Plan REJECTED for Underground fire main for 218,477 SF Hospital. 8" main being supplied from Fire Pump Room located in the CEP building, 8" DCDA BFP leading into the hospital and finishing 1' AFF. Stand alone 5" Storz FDC with 8" line teeing off of the fire main.

Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: Stuart Schnellenberger 904-209-1778, SSchnellenberger@SJCFL.US

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

 

1. Florida Administrative Code (FAC) 61G15-32.002 defines a material deviation as "Any deviation from the design parameters established and documented by the Engineer of Record." Furthermore FAC 61G15-32.003(6) states "When layout documents contain material deviation from the Engineer of Record's Fire Protection System Engineering Document, such layout documents are not compliant unless they are accompanied by revised Engineering Documents made and sealed by the Engineer of record for the Fire Protection System."

According to the shop drawing provided, the hospital's fire main being supplied after the fire pump for the hospital is an 8" line. However, Page FP100 of the Fire Protection Site Plan from Construction Documents Volume 3 MEPT, shows a 6" line coming from the fire pump. Please clarify which diameter line is going to be used for the fire main after the fire pump to lead into the hispital. Be advised, the sizes of FDC line and the backflow preventer may need to be changed as well if changes are made. Please show on the shop drawings.

 

2. Backflow preventers serving fire sprinkler systems are required to be electronically monitored. Please indicate how this is going to be achieved.

If conduit is going to be used, please show it on the shop drawings.

Please coordinate with the fire alarm contractor.  

 

3. Please provide how the FDC is going to be configured to be kept dry. If a bell drip valve is going to be used with the check valve, please indicate it.

 

4. Since there are multiple buildings on this site, provide signage indicating the building that the FDC serves.

 

5. RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 8th Ed.