| | Department Issues | Signed Off | Intl |
|
|
Plans for a 6 story hospital with 77 private beds, submitted and reviewed as a Healthcare occupancy. The building will be constructed as Type IA(I332) and will be provided with fire sprinklers, a fire alarm, standpipes, a fire pump, and a smoke management system. The building square footage is 218,477 with the following breakdown:
1st floor- 61,528sf 2nd floor- 55,972sf 3rd floor- 34,125sf 3rd floor mechanical penthouse- 4,537sf 4rh floor- 26,936sf 5th floor- 26,936sf 6th floor mechanical penthouse- 8,443sf
Reviewed using FFPC 7th edition effective Dec. 31, 2020. Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code. For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us. To schedule fire i
|
12/8/2023
| RDowling |
|
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the Permit Center. B. Once at the Permit Center swap out altered pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8". - Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)
When you resubmit, break down the response to comments by volume, due to the size of the plansets.
|
11/16/2023
| PWebb |
|
|
1) In Building Radio Enhancement System (BDA) See also FS633.202(18)
This building is required to have a third party contractor conduct a two-way radio communication test in accordance with NFPA 1:11.10 and NFPA 1221 (2016 ED.) by the time of the framing inspection.
St Johns County Fire Rescue’s radio control frequency is 853.8875. You will need to provide this information to your third party contractor.
NOTE: A copy of this report must be provided and submitted to our office as a revision before the 105 framing inspection. A 105 Framing Hold has been placed until receipt of the revision.
-If it passes the inspection radio testing at the framing stage, you will need to submit as a revision as we will record the documentation and remove the hold.
- If the third party paperwork indicates the test is not satisfactory, then the contractor will have to submit for a revision. The revision will need to include: the unsatisfactory test paperwork, outline of corrective measures, and plans to illustrate the corrective measures to meet requirements provided by the design professional.
At the final, you will be required to provide satisfactory testing by the third party contractor following the installation of the in building radio enhancement system.
--------------
Thursday, November 16, 2023 PJW- Per RTC "Will Comply".
|
11/16/2023
| PWebb |
|
|
2) INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system: - Fire alarm system (supervise sprinklers) - Fire sprinkler system (Supervised) - Fire underground - Kitchen hood - Kitchen suppression system - Fire/smoke damper inspections - Fire Pump - In-Building Radio Enhancement System (BDA) TEST / PERMIT - Smoke Control System - Medical Gas Inspection prior to final - Revision for Stairway identification signage plans (See comment 7) - Clean agent System (Novec 1230) - Revision for special door locking arrangements - Revision for laboratory chemical submittal and compliance with NFPA 45. - NFPA 801 Engineers Analysis/Report - 3rd party NFPA 801 inspection
|
11/16/2023
| PWebb |
|
|
3: Does this facility utilize cryogenic systems per NFPA 1:63.4.5?
-------------------
Thursday, November 16, 2023 PJW- Per RTC, the only cryogen is contained in the UL listed MRI equipment.
|
11/16/2023
| PWebb |
|
|
4) The door schedule is missing the card reader designation on some doors as follows per the hardware schedule:
1300.11 HW131 1514 HW131 1512 HW131
Also add delayed egress on the door schedule for the following doors and any other missing:
S2.3 S2.4 S1.4
-----------------------------------
Thursday, November 16, 2023 PJW- Per RTC the A9 series plans have been updated to include this. Ensure that this information is provided when submitting for the special door lock revision. A hold has been added to the permit for this revision.
|
11/16/2023
| PWebb |
|
|
5) Doors 2301, 2410, and 3205.1 are indicated in rated walls and do not indicate a door rating in the door schedule.
----------------
Thursday, November 16, 2023 PJW- Door ratings updated on the A9 series sheets.
|
11/16/2023
| PWebb |
|
|
6) Informational Note: No response necessary
No stair-reentry is required per NFPA 101:18.2.2.2.10
|
11/16/2023
| PWebb |
|
|
7) Demonstrate stairway identification signage on the plans as required by NFPA 101:7.2.2.5.4.1.
-----------------
Thursday, November 16, 2023 PJW- Per RTC "Will comply. These signs will be included in the signage and wayfinding package to be issued at a later date." A hold has been placed on the permit for a revision to address this.
|
11/16/2023
| PWebb |
|
|
8) Is NFPA 232 "Standard for the protection of Records" being applied to this project per NFPA 232:1.1.7? If yes, what is the classification of records storage? 232:1.1.6
-------------
Thursday, November 16, 2023 PJW- Per RTC, NO, records are electronic, paper records will not be stored at this facility.
|
11/16/2023
| PWebb |
|
|
9) The common path of egress is exceeded from the kitchen area, therefore a second means of egress is required from this space. Also provide exit and exit access signage accordingly. NFPA 101:18.2.5.5.2, 18.2.5.3.
------------------
Thursday, November 16, 2023 PJW- Pathway has been identified through the server, AL201 has been updated, exit sign added above 1130.1.
|
11/16/2023
| PWebb |
|
|
10)Med gas is indicated and is provided on sheets sealed by Benjamin D. Roseborough PE.
Med Gas is required to comply with NFPA 99. Med Gas can be but not limited to oxygen, nitrous oxide, compressed air, carbon dioxide, medical-surgical vacuum. Due to the inexperience dealing with med gas, the Fire Marshal's office will require Technical Assistance by an approved independent third party with expertise in this area as permitted by NFPA 1 Chapter 1.15 at the submitter's expense. Please follow the steps below for submittal.
e) Following the installation of the medical gas (and prior to the fire final), a third party inspection will need to take place. The third party reviewer may also be the inspector. The third party inspector shall provide written documentation to the Fire Marshal’s Office at time of fire final that the med gas inspection was conducted and the system inspected per the plans meets the requirements of the Code. If documentation is provided stating that the system does not meet the requirements of the code and corrective action is needed, the Owner will need to work with their design professional and third party to resolve the issues. Our office will not complete the fire final prior to the third party acceptance. A hold has been placed on the permit prior to final for this inspection report.
-----------------
Thursday, November 16, 2023- PJW- Per RTC " Will Comply".
|
11/16/2023
| PWebb |
|
|
11) Will you be providing gaseous fire protection in the data/server rooms?
-----------------
Thursday, November 16, 2023 PJW- Per RTC, Yes, a Novec 1230 system will be provided. A hold has been place on the permit for this submittal.
|
11/16/2023
| PWebb |
|
|
12) Do not see where cooking oil (new and/or used) will be stored. If inside the building, show compliance with 1:66.19.7. If outside the building, indicate tank size (in gallons) and be prepared to submit for tank permit if over 60 gallons. Permit will need to show compliance with NFPA 1 Chapter 66 (1:66.9.19, 1:66.21) for a combustible IIIB liquid.
-----------------------
Thursday, November 16, 2023 PJW- Per RTC, 20 gallons of new cooking oil will be stored in Dry Catering 1116. Used oil is immediately taken off site by a third party service.
|
11/16/2023
| PWebb |
|
|
13) Will CO2 beverage system exceed 100 pounds? If so, demonstrate compliance with NFPA 55:13.10.
NOTE:Make sure to include CO2 tank location, CO2 piping to mixing location (ex- bag/box), indicate which option will be used (ventilation vs sensor/notification) AND show compliance with chosen option of compliance. If Sensor/notification, show locations of the devices.
---------------------
Thursday, November 16, 2023 PJW- Pet the RTC, the owner only anticipates 80lbs maximum. This will be verified at final.
|
11/16/2023
| PWebb |
|
|
14) The overall reflected ceiling plan (RCP) shows exit signage, the partial RCP's do not. Ensure that all plans match.
---------------------
Thursday, November 16, 2023 PJW- The partial RCP's have been updated to show the signage.
|
11/16/2023
| PWebb |
|
|
15) Informational, no response necessary
The FP pages are sealed by Benjamin D. Roseborough PE
A fire pump is indicated, supervised sprinkler system is indicated on sheet FP001(g).
|
11/16/2023
| PWebb |
|
|
16) INFORMATIONAL ONLY NO RESPONSE NECESSARY: At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:
- wall and ceiling finish will meet Class A throughout. 101:18.3.3.2. 1:20.4.3.2
- walls and ceiling shall are permitted to be meet class A or B in individual rooms with a capacity of 4 or less people. 101:18.3.3.2.1 1:20.4.3.2.1
- corridor wall finish not exceeding 48in in height that is restricted to the lower half of the wall shall be permitted to be class A or B. 101:18.3.3.2.2. 1:20.4.3.2.2
- floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:18.3.3.3.3. 1:20.4.3.3.3
- floor finish in exit enclosures and exit access corridors and spaces open to them must meet Class I or Class II. 101:18.3.3.3.2 1:20.4.3.3.2
- draperies, curtains, and other loosely hanging fabrics and films serving as furnishings and decorations shall meet test method 1 or 2 of NFPA 701. 101:18.7.5 1:20.4.2.5.1
If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.
|
11/16/2023
| PWebb |
|
|
17) Will this facility store, handle or use radioactive materials in quantities or under conditions that require government oversight? If so, indicate location within facility and compliance with NFPA 801 (2008) will need to be checked. 45:1.1.1.
---------------------------------------
Thursday, November 16, 2023 PJW- The response to comments indicates that a small amount of radioactive material will be stored on site in a lead lined cabinet, and that it will be licensed by the state. This is per NFPA 801:1.3 in which compliance with this standard is required.
The requirements of this standard are detailed and include the need for policy creation of a fire hazard analysis, a fire protection program, development of an emergency response plan, creation of a facility fire organization, and a pre incident fire plan. There are also requirements that may affect the design of the building etc.
Due to the complexity and unusual nature of the hazard, our office is requiring that a third party engineer with expertise in the nuclear field evaluate the facility, conduct an analysis and provide a report with any recommendation of changes, in addition to whatever else is required by NFPA 801 in totality. In addition a 3rd party inspection will be required. A hold will be placed on framing (105) for this report, inspection, and any subsequent changes to the building that may be required resulting from the analysis. The authority for this requirement per NFPA 1:1.15.1.
|
12/8/2023
| RDowling |
|
|
18) Darken the rated wall indications on the mechanical plans so they stand out as indicated on the legend. Currently the indication is light.
--------------------
Monday, November 20, 2023 PJW- The RTC references the "life safety wall legend" on the bottom of the sheets. I see the wall legend, but as mentioned above the actual wall symbology is lighter than the legend itself so it is difficult to identify the rated walls on the sheets. Please darken the wall symbology on the plans to match the darkness of the legend.
|
12/8/2023
| RDowling |
|
|
19) Stair S2
It appears that there is an exit sign on the 1st floor leading into the building. The stair needs to discharge directly outside as indicated by the exit signage over the exterior door from S2. Is the sign mentioned intended to be a directional exit access sign guiding people to the exterior door?
|
11/20/2023
| PWebb |
|
|
20) Provide Lighting on the LS branch in all locations where patients will be occupying for procedures treatment etc. for longer durations such as CT, MRI, Stress Treadmill, Nuclear Med, Peds Trauma 1339, Trauma 1338, Operating rooms etc.
--------------
Monday, November 20, 2023 PJW- Per RTC the locations mentioned above will be powered from the critical branch which is level 1 priority and will activate within 10 seconds of normal power loss. In addition the operating rooms connected to the critical branch have battery backup which complies with NFPA 99:6.7.5.1.3.2.
What you are referring to sound like you are describing the Life Safety branch, but referencing the critical branch. The critical branch is for task illumination, receptacles, fixed equipment etc. The LS branch is for egress lighting, illumination of means of egress and emergency lighting. Ensure that lighting from the LS branch is provided in the originally mentioned locations.
|
12/8/2023
| RDowling |
|
|
21) Identify for me or direct me to if already provided, what the life safety branch provides power to in accordance with NFPA 99:6.7.5.1.2.4, and 6.7.6.2.1.5(c)
Monday, November 20, 2023 PJW- Per RTC:
1. Egress lighting 2. Emergency Lighting 3. Fire Alarm 4. Elevator Cab lighting and controls 5. Med gas alarm system 6. Automatic (electrically powered) doors 7. BDA
It is also noted that the generator and transfer switch loads are part of the Central Energy Plant (CEP) project. The above can be found on the E100 series plans.
|
11/20/2023
| PWebb |
|
|
22) List the locations in the building in which deep sedation and general anesthesia are administered and provide battery backup emergency lighting units in these areas. Show lighting on the plans. NFPA 99:6.3.2.6.1.
-----------------
Monday, November 20, 2023 PJW- Locations provided in the RTC.
|
11/20/2023
| PWebb |
|
|
23) Provide Life Safety branch emergency lighting in the following locations:
- Giftshop - Security 1175 - Passage 1176 - Facility engineering shop 1416 - Biomed shop 1412 - Receiving 1429 (egress through) - Physician lounge 2105 - Clinical control 2150 - Men's locker room 2271E - Woman's Locker room 2273E - 2nd floor pharmacy area - Hematology coagulation - L&D - Mechanical penthouse Level 3 - ISOL/treatment bay area 4th floor - Therapy Gym 5100
NFPA 101:18.2.9.2
--------------------------
Monday, November 20, 2023 PJW- LS branch lighting has been provided in the above locations indicated on sheets E101A, E101B, E102A, E102B, E103A, E104A, and E105A.
|
11/20/2023
| PWebb |
|
|
24) Second floor atrium
I do not see any LS branch lighting at the top of the atrium. Provide and identify lighting. NFPA 101: 18.2.9.2
-------------------
Monday, November 20, 2023 PJW- Lighting provided from the LS branch on sheets E102A and E102B
|
11/20/2023
| PWebb |
|
|
25) Should there be an exit sign located at the intersection of corridor 3200.5 and 3200.3 facing plan south with dual chevrons?
-----------------
Monday, November 20, 2023- Exit sign added.
|
11/20/2023
| PWebb |
|
|
26) Some doors leading into stairwells have perpendicular directional signage only pointing to the door and some only have signs parallels to the door mounted over the doorway with no perpendicular sign pointing to it. For the latter, ensure that the parallel (flush on wall) sign is visible from the corridor leading to it. Perpendicular signage may be necessary for visibility.
-----------------
Monday, November 20, 2023 PJW- Perpendicular signage added.
|
11/20/2023
| PWebb |
|
|
27) 3rd floor elevator lobby at family lounge 3105
The egress path that passes the elevators from plan north to south only seems to have 1, D1A fixture near it. Will this provide enough LS branch coverage for the egress path?
------------------
Monday, November 20, 2023 PJW- Additional downlighting has been provided on the LS branch. Sheet E103B.
|
11/20/2023
| PWebb |
|
|
28) Exit sign on 4th floor near stair S1 needs a chevron.
---------------
Monday, November 20, 2023 PJW- Chevron added to sheets A604AB.
|
11/20/2023
| PWebb |
|
|
29) Smoke Control System
Demonstrate compliance with NFPA 92 and NFPA 204, engineering guides, or recommended practice per NFPA 101:9.3.1. A hold has been placed on this permit for this submittal or revision to address this.
-----------------
Monday, November 20, 2023 PJW- Per RTC, the rational analysis document will be provided for review. A hold has been placed on the project for this information.
|
11/20/2023
| PWebb |
|
|
30) Smoke control system, system design
The engineer of record shall clearly identify the intend of the system, design methods used, the appropriateness of the method, and the required means of inspections, testing and maintaining the system. A hold has been placed for this submittal or revision to address this.
Ensure that this complies with 8.6.7(5).
---------------
Monday, November 20, 2023 PJW- Per RTC, will comply. Rational analysis document will be provided.
|
11/20/2023
| PWebb |
|
|
31) Smoke control system
Acceptance testing shall be performed by a special inspector in accordance with 9.13, in parallel with our office. NFPA 101:9.3.3. After completed the associated documentation/report will need to be provided to your inspector prior to final issuance.
-----------------------
Monday, November 20, 2023 PJW- Per RTC, will comply.
|
11/20/2023
| PWebb |
|
|
32) Does this building include a roofing system that involves combustible supports, decking or roofing? If yes demonstrate compliance with NFPA 101:18.1.6.2, 18.1.6.3.
Also demonstrate compliance with NFPA 101:18.1.6.4, .5, .6, and .7 as it relates to minimum construction requirements. If already provided within structural sheets, guide me to the locations. Our office does not review structural sheets.
----------------
Monday, November 20, 2023 PJW- Per RTC, No, as stated on sheet G0101, the construction type is non-\combustible type 1A
|
11/20/2023
| PWebb |
|
|
33) On the door schedule, identify the applicable doors that fall under the requirements of delayed egress, sensor release of electrical locking systems, or locks for the needs of patients per 101:18.2.2.4 or 18.2.2.2.5.2, 18.2.2.2.6. For doors meeting 18.2.2.2.4 provide all component specifications demonstrating requirements for the applicable arrangement code section. Any doors secured for the clinical needs of patients, show compliance with these sections as well. 18.2.2.5.2, 18.2.2.2.6.
If you are unable to provide the amount of detail requested at this time, indicate this and it can be addressed by a revision later. This may be the better option due to the size and complexity of this building, in addition the installing contractor would be involved to provide the needed information (plans, specification, etc.)
----------------
Monday, November 20, 2023 PJW- RTC indicates.. "yes, there will be delayed egress in portions of the hospital that must be secured during normal operation. Any delayed egress being provided will be compliant with 18.2.2.2.4 and 7.2.1.6.1. Delayed egress openings are identified and described in the door hardware specification 087100 as well as on the Technological drawings. Additional information can be provided once final hardware is submitted by the supplier/installer and approved by architect.
Monday, November 20, 2023 Reviewer response PJW- A hold will be placed on the permit for a revision to address the specifics of any special locks including or in addition to what is indicated in the response. Ideally we would like to see a clean floor plan showing only the special locks that are being submitted for. This includes all locations in accordance with 18.2.2.4 and any doors that will be locked down for the needs of the patients per 18.2.2.2.5.2. Or any magnetic type locks with card access. Also please note that the 087100 manual section was not provided with the resubmittal. I will need that when you submit. With a building this size please make the submittal sheet as clean as possible without a lot of the underlying layers that may clutter it. Contact me if you have any questions.
|
11/20/2023
| PWebb |
|
|
34) Are the doors in Pre/Post OP 2264, 2262, 2260 and similar horizontal sliding doors in accordance with 18.2.2.11.2 or powered sliding doors in accordance with 7.2.1.9.1? If doors are powered, the break free feature of 7.2.1.9.1.5 appears to be signified going into the room, not out. Demonstrate the remainder of 7.2.1.9 requirements. Same applies to NICU private rooms and all sliding doors.
------------------
Monday, November 20, 2023 PJW- Per RTC the doors are manual sliding doors that comply with 18.2.2.2.11.2 that latch and do not rebound.
Just verify that the occupant loads do not exceed 10 in these areas.
|
11/20/2023
| PWebb |
|
|
35) Door S2.1 HW group 56, which side is the secure side?
----------------
Monday, November 20, 2023 PJW- The door is staff access to stair only, not egress. The corridor side is secured. Occupants egress through the elevator lobby.
|
11/20/2023
| PWebb |
|
|
36) Treatment room 3153 (A203B2) requires a minimum 41 1/2" door per 18.2.3.6.
------------------
Monday, November 20, 2023 PJW- Per RTC the above is for the treatment of infants. Per 18.2.3.7(3) a minimum clear width of 32" can be provided where serving newborn nurseries and treatment areas. Any adult treatment occurs in the patient rooms.
|
11/20/2023
| PWebb |
|
|
37) What is pediatric multipurpose room 4110 (4th floor) used for? Does it fall under the requirements of NFPA 101:18.2.3.6?
------------------
Monday, November 20, 2023 PJW- Per RTC, the rooms have been increased to 44" The room description is indicated in the RTC.
|
11/20/2023
| PWebb |
|
|
38) Are mechanical penthouse 3500 and the 6th floor mechanical penthouse "normally unoccupied building service equipment support areas" as per NFPA 101:7.14? If yes, label them as such. Do they contain any high hazard contents or operation, or fuel fired equipment or storage of combustibles?
-----------------
Monday, November 20, 2023 PJW- Per RTC, No, they are not normally occupied. Please label them as such per the comment above. Also will there be fuel fired equipment?
|
12/8/2023
| RDowling |
|
|
39) 6th floor mechanical penthouse has an exit sign indicted on the plan upper door that leads out to the roof. Where does this lead?
-------------------
Monday, November 20, 2023 PJW- Per RTC the pair of doors leads to the roof to the north if the southern egress was obstructed. To the north personnel could re enter the exit stair vestibule. The doors will always allow free ingress to the stairs.
|
11/20/2023
| PWebb |
|
|
40) What is stored in general storage 1420 and how will it be stored (racks, high piles storage). Will there be any flammable or combustible liquids or hazardous materials stored here or anywhere else in the building aside from the laboratories which are handled by their NFPA standard? Apply 101:8.7.3.1 as necessary. 101:18.3.2.7
----------------
Monday, November 20, 2023 PJW- Per RTC, general medical supplies required for patient care. Storage on open wire shelving and some low pallet racks. No flammable/combustible liquids or hazmat.
|
11/20/2023
| PWebb |
|
|
41) The plans indicate that motion sensors will be used in the areas of egress. At time of fire final be prepared to show compliance with NFPA 101 7.8.1.2.2:
(1) switch controllers must be listed (2) switch controllers equipped for fail-safe operation and evaluated for this purpose (3) timers be set for a minimum 15 minute duration. (4) motion sensor be activated by any occupant movement in the area served by lighting units (5) If building has a fire alarm, activation of fire alarm must activate the switch controller (6) lighting control device may not turn off any lights realized upon for activation of photo luminescent exit signs or path markers (7) Lighting control devices may not turn off any battery equipped emergency luminaries, unit equipment or exit signs
--------------------
Monday, November 20, 2023 PJW- Per RTC the egress lighting will not be controlled by occupancy sensors, they will be on 24/7. Also the patient floor corridors will have relays. The above requirements will be verified at final.
|
11/20/2023
| PWebb |
|
|
42) Doors 3100.0 swing against egress per the LS plan.
----------------
Monday, November 20, 2023 PJW- The door swing has been reversed indicated on sheets AL203, A203, A203B1, and A203B2.
|
11/20/2023
| PWebb |
|
|
43) Egress from corridor 3100.4 travels through family lounge 3105 to get to the egress stair. Egress cannot pass through intervening rooms per NFPA 101:18.2.5.4. Same issue on the 4th and 5th floors lounges 4100 and 5110. These spaces do not appear to meet 18.3.6.1.
------------------
Monday, November 20, 2023 PJW- The RTC indicates the following.."The corridor continues to the south past the Family Lounge. Per NFPA 18.3.6.1(1) the Family Lounges can be open to the corridor as they meet all of the criteria of (a) through (d). "Spaces shall be permitted to be unlimited in area and open to the corridor, provided that all of the following criteria are met..."
Monday, November 20, 2023 PJW Reviewer Response- The 18.3.6.1(1) reference provided is regarding just what it says, spaces that are permitted to be open to the corridor as it relates to protection of the corridor. That is a separate requirement from the section originally in question which is NFPA 101:18.2.5.4 which is regarding means of egress which states..."Every corridor shall provide access to not less than two approved exits in accordance with sections 7.4 and 7.5 without passing through any intervening rooms or spaces other than corridors and lobbies." Corridor 3100.4 continues through the family lounge to get to the exit stair. Since the family lounge is not a corridor or a lobby, it is a intervening space per this section, which is not permitted. I see two options for compliance. Option 1: continue corridor 3100.4 south past the family lounge essentially creating a wall separating the lounge from the corridor with a door leading into the lounge. This would alleviate passing through the lounge. Option 2: If travel distance and other egress calculations allow, the door leading into the family lounge from corridor 3100.4, instead of exit signage directing occupants through the family lounge, direct them by chevron to plan left towards the hallway to the left of the stairs to continue down and around to the stair. Make sure the measurements work and demonstrate. It appears that that section of corridor is used already labeled and utilized form plan left.
|
12/8/2023
| RDowling |
|
|
44) Suites
The clinical control center 2150 (specifically PBX room 2151, and supervisors office 2150A) do not appear to meet 18.2.5.6.1. Is this intended to be classified as a non patient care suite per 18.2.5.7.4. If yes identify it on the plans as such.
Same applies to the following:
- Med staff area 2109B, 2109A, 2105A, 2109. - Sleeping rooms 2269A, 2269B per 18.2.5.7.2(2), 18.2.5.7.4 - 3rd floor section 3120 - female/male locker 3271G, 3271B. - supervisors office 4209A/ Assy clean room 4212 - treatment area 4206 (treatment ISOL 4206A) - Sleeping rooms 4204B, 4204C, Workroom 4202. - Mgr office peds 4111A.
---------------
Monday, November 20, 2023 PJW- Per the RTC, these are non patient care suites. Sheet AL202 has been updated to reflect this. The other areas listed have also been clarified as suites on the revised AL series life safety plans.
|
11/20/2023
| PWebb |
|
|
45) Travel distance from the kitchen suite starting point (as indicated on AL201) exceeds 200 feet to all exits, including vestibule 1000.1, doors 1000.6, doors 1400 and vestibule 1300.11.
----------------------
Monday, November 20, 2023 PJW- Per the RTC, sheet AL201 has been updated to clarify the distances. It does not appear that the measurements provided start where required by the code, however using the original travel distance starting point, since egress was not added through the server, this requirement is met.
|
11/20/2023
| PWebb |
|
|
46) The code summary identifies NFPA 45 for laboratories using chemicals. Identify on the plans where these laboratories are located so I can verify compliance with the standard. Also provide chemical SDS sheets and MAQ's etc.
------------
Monday, November 20, 2023 PJW- Per the RTC, the laboratory is on the 2nd floor southwest portion of the plan. The final equipment selections and chemicals used are not yet determined. Will be provided at a later date. A hold has been placed on the permit for this revision.
|
11/20/2023
| PWebb |
|
|
47) Will this facility have hyperbaric chambers? NFPA 101:8.7.5
-------------
Monday, November 20, 2023 PJW- Per RTC, NO.
|
11/20/2023
| PWebb |
|
|
48) Will there be any cooking equipment outside of the kitchen? NFPA 101:18.3.2.5.
-------------
Monday, November 20, 2023 PJW- Per RTC, No.
|
11/20/2023
| PWebb |
|
|
49) Identify accumulation space per 101:18.3.7.5.
---------------
Monday, November 20, 2023 PJW- Provided on Life Safety Plans.
|
11/20/2023
| PWebb |
|
|
50) Identify the risk category on the code summary per 99:4.1. It appears to be category I per this section. If not, identify what classification applies and provide a risk assessment. NFP A99:4.2.2.1, 4.2.3.
-----------
Monday, November 20, 2023 PJW- G010 revised to indicate category 1.
|
11/20/2023
| PWebb |
|
|
51) New Comment
When resubmitting, ensure that all plans are securely bound. With a plan-set of this size it is extremely difficult to process when loose. Our office will not review the resubmittal if loose.
|
| |
|
|
52) New Comment Thursday, November 30, 2023 PJW
The CEP building contains the fire pump that will supply the hospital. The CEP fire pump will need to have an approved pump final inspection by our office and the CEP building will need to be finaled and CO'd prior to the hospital sprinkler final inspection being completed. A hold has been placed on the permit for this.
|
12/8/2023
| RDowling |