SJC Home
Clearance Sheet C2021-007496

 Department IssuesSigned OffIntl

Plan submitted for 1056sf in a construction type VB non sprinkler building of unknown occupancy type to be used for oil changes.  G-0.3 shows that new and used class IIIB liquid will be stored in 2950 gallons between 16 tanks. Reviewed as new special purpose industrial using FFPC 7th edition effective January 1, 2021.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

 

1) This is a preliminary review. Do not resubmit until clearance sheet obtained.

NOTE: Based on fire's site review, additional comments may be provided.

 

2) Provide occupancy type in accord with FFPC. 1:30.2.2

 

3) Page A1.2 shows the color of paint the concrete floors in garage area will be painted. Identify permanent slip resistant nonabsorbent paint type. 1:30.2.5

 

4) Provide spec sheets for each of the 3 containers shown on G-0.3. I am looking to see that a) the type container is allowed by FFPC and b) the container size meets the container type in FFPC 1:66.9.4.3.

 

At time of fire final:

- atleast 1 portable extinguisher having a capability of not less than 40:B shall be located outside of but not more than 10' from door opening into a liquid storage area. 1:66.9.10.2.2

- completed on site emergency plan procedures is to be on site that meets 1:66.21.6.5.

- NFPA 704 placarding applied to storage tanks containing IIIB liquids. 1:66.21.7.2

 

5) Where are the 16 tanks going?