SJC Home
Clearance Sheet C2021-006778

 Department IssuesSigned OffIntl

Plan reviewed for revision of emergency lighting to approved plans.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

**********************************

Tuesday, August 9, 2022  DF: Review of 1st resubmittal.

8/9/2022 dfeagle

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

8/9/2022 dfeagle

1) An emergency light was removed on sheet E-101 and E-102 in the Entry Porch (was not clouded).

This EL is required for coverage.

8/9/2022 dfeagle

2) The exit sign/emergency light combo in the covered gathering space is required.

Return the exit sign/emergency light combo.

8/9/2022 dfeagle