| | Department Issues | Signed Off | Intl |
|
|
Plans for a 95 head NFPA 13 Wet fire sprinkler system for a shell building with 1 remote area. The system is designed as Ordinary Group 2, .20 density. The exterior seating area is being protected with dry barrel sidewall heads.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. Reviewer: PJ Webb 904 209 1744 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
5/25/2022
| agedris |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
5/25/2022
| agedris |
|
|
1) Provide material data sheets for all system components.
--------
Not provided with resubmittal. PJW Monday, December 20, 2021
|
5/25/2022
| agedris |
|
|
2) The riser diagram shows a yard FDC that is tied into the riser. The approved underground plans indicate that the FDC is mounted on the backflow.
--------
Plans changed to show backflow mounted FDC. PJW Monday, December 20, 2021
|
12/20/2021
| PWebb |
|
|
3) Identify the relief valve or air reservoir on the plans/riser diagram. Provide specs. NFPA 13:7.1.2.
---------
Do not see addressed. Identify on the riser diagram and/or provide manufacturers specification sheets. PJW Monday, December 20, 2021
Relief valve added to sprinkler riser detail AGEDRIS Wednesday, May 25, 2022
|
5/25/2022
| agedris |
|
|
4) The building plans indicate that the riser will be heat traced to protect it from freezing. Provide specifications for the proposed product. Ensure that allowances are made for fire alarm monitoring of the heat trace.
---------------------
Sprinkler plans revised to indicate that the heat tracing is by others, however I still need the specifications now in order to approve your plan. PJW
Heat tracing removed, Electric Heater being added to riser room. AGEDRIS Wednesday, May 25, 2022
|
5/25/2022
| agedris |
|
|
5) The head spacing indicated on the calculations and the sprinkler criteria is 130sf per head maximum. The head spacing indicated on the plans appears to exceed this.
--------------
Based on the printed scale the head spacing indicated still exceeds the maximum 130 as permitted by the hydraulic calculations and sprinkler criteria. If the scale is off, you can provide a dynamic scale on the plans, provide dimensions, or reprint the sheet to scale. PJW Monday, December 20, 2021
130 sq ft spacing is still valid some sprinkler heads were adjusted to maintain proper spacing. AGEDRIS Wednesday, May 25, 2022
|
5/25/2022
| agedris |