Mike Jolly-Miranda Contracting Class V 388-1121 x303

All fire protection that requires inspection from Fire Marshal's Office are highlighted on the plan. This includes 7 private RED fire hydrants and 2 fire sprinkler lines.

(Greenwise: 8" DCDA with FDC to approx. 100 feet of 8" DR-18 to in-building riser)

(Retail: 8" DCDA with FDC to approx. 50 feet of 8" DR-18 to in-building riser)

2/1/2021 SMurray

Fire Hydrant shall: 
- painted red to indicate private (LDC 6.03.03.C.10)
- set on flat stone or concrete slab (NFPA 24:7.1.3)  
- outlet threads are NHS external threads (NFPA 24:7.1.2)  
- center hose outlet not less than 18 in. above final grade and facing the roadway (NFPA 24:7.3.3)

2/1/2021 SMurray

To schedule a fire inspection BEFORE cover up of pipe, use the automated system: please call 904-827-6842 press 1, enter building permit _____ and enter appropriate code for sprinkler underground visual(638), sprinkler underground hydro(605), sprinkler underground flush(637)
OR call 904-209-1740 press 1, then press 2.

INFORMATIONAL: Your permit fee includes the cost of review, one hydrostatic test inspection and one final inspection. If you will require more than one hydro/visual inspection you will need to call 209-1740 x 1 to arrange payment.  

2/1/2021 SMurray