Plans for 2 kitchen suppression systems as follows:

Rotisserie Hoods
2, 13' hoods abutted side by side
Ansul R102 3 gallon
Using 8 out of 11 flow points
plenum and duct protection only. 

Pizza hoods
2, 7' hoods abutted front to back
Ansul R102 3 gallon
Using 4 our of 11 flow points
plenum and duct protection only


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

6/7/2022 PWebb

Need specification sheets for the stacked rotisserie which is a Hardt Inferno 4500.  I cannot find the specs online, it is believed that this model may be a Costco exclusive.  Since it is a Canadian company which may prove challenging to get specification sheets, I provided an option to send me pictures of the data plate indicating the make/model and the UL/ETL listing tag.   Holding plans until Monday. 

------------

Tuesday, June 7, 2022 PJW- Still awaiting information.  Per supervisor approving plan, ensure that listed equipment is installed.  This will be verified at final. 

6/7/2022 PWebb