Clearance Sheet C2021-006070

 Department IssuesSigned OffIntl

Plans for a revision to the following sheets with a detailed revision narrative for the following sheets: TS101, G101, G201, G202, SD101, SD201, SD203, A101, A201, A202.1, A301, A401, A501, A501.1, A501.2, A501.3, A501.4, A501.5, A501.6, A502, A502.1, A502.2, A503, A504, A504.1, A505, A505.1, A505.2, A506, A506.1, A507, A508, A509, A510, A512, A601, A601.1, A602, A602.2, A602.3, A701, A702, A703, A703.1, A704, A704.1, A704.2, A704.3, A704.5, A704.6, S0.4, S1.0, S1.1, S1.2, S1.3, S1.4, S2.1, S2.3, S3.1, S3.2, S4.0, S4.1, S5.2, P0.2, P1.1, P2.1, P3.1, P3.2, P4.1, P4.2, P5.2, M0.1, M1.1, M2.1, M2.2, M3.1, M3.2, E2, E4, E5, E7, E9, and E10. 

Note, is spoke to the design professional to clarify the exterior door locks since the revision indicates electromagnetic locks.  He clarified that the Von Duprin DE5300 delayed egress system will be installed but not turned on/ activated until notified by Costco. The system does meet the requirements of the code if it is set up correctly.  I would reach out to your fire inspector prior to final to see what they will allow as it relates to this as it relates to testing/signage etc.  I would be prepared to test the system.   


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

5/19/2022 PWebb