SJC Home
Clearance Sheet C2021-006070

 Department IssuesSigned OffIntl

Plans for a 1274 head fire sprinkler system for Costco.  In order to begin the review, our office needs the following information. 

- Overall system plan with each different system color coded for clarity, showing each system from the pump room to the furthest head. 

- Overall plans for each system.

- Closer up detail sheets for each system (similar to what was provided with the review). 

- The plans submitted show the system information with a blank background.  Include underlying floor plan information/layers for walls, room names, identifying features, shelving etc. so I can orient the system with the building and verify coverage.   

- Shelving construction.  NFPA 13 sections as referenced in the design criteria have specific requirements/options for the shelving.  Provide a general note indicating that the shelving will be installed in accordance and quote the specific sections of NFPA 13 or provide shelving details/specs demonstrating compliance.

 

 

Reached out to contractor and the Costco consultant for this information. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.
To schedule fire i