SJC Home
Clearance Sheet C2021-006070

 Department IssuesSigned OffIntl

 

Plans for a preliminary review of a 157,522sf Class A Mercantile Occupancy that will be provided with fire sprinklers supplied by a fire pump, and a fire alarm system.  There will also be a tire storage area with tire installation bays.  The building is constructed as Type VB.  The total occupant load is 2207. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

-----------------------------------------------------------

The resubmitted plan also includes revisions to the following sheets:

G101, SD101, SD203, SD301, A101, A201, A301, A401, A501, A501.1, A501.2, A501.3, A501.4, A501.6, A502.1, A503, A505, A505.1, A505.2, A506.1, A509, A701, A704 and A704.4.  A revision narrative was included with the response to comments.  This was marked office so it will be scanned into the system.  Note: sheets not stamped revised since they are included with the original approved plans.  PJW Monday, September 20, 2021

9/20/2021 PWebb

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

9/20/2021 PWebb

1) This plan cannot be approved until a clearance sheet is issued. 

--------------

Clearance sheet obtained.  PJW Monday, September 20, 2021 

9/20/2021 PWebb

2) Sheet G101

Remove the note that states "Fire Marshal shall determine size and type of fire extinguishers".  This is the responsibility of a licensed fire extinguisher contractor.   FSS 633.304

-------------

Note changed, FM reference removed.  PJW Monday, September 20, 2021

 

9/20/2021 PWebb

3) In Building Radio Enhancement System (BDA)

This building is required to have a third party contractor conduct a two-way radio communication test in accordance with NFPA 1:11.10 and NFPA 1221 (2016 ED.) by the time of the framing inspection.

St Johns County Fire Rescue’s radio control frequency is 853.8875. You will need to provide this information to your third party contractor.

NOTE: A copy of this report must be provided and submitted to our office as a revision before the 105 framing inspection.  A 105 Framing Hold has been placed until receipt of the revision.

-If it passes the inspection radio testing at the framing stage, you will need to submit as a revision as we will record the documentation and remove the hold.

- If the third party paperwork indicates the test is not satisfactory, then the contractor will have to submit for a revision. The revision will need to include: the unsatisfactory test paperwork, outline of corrective measures, and plans to illustrate the corrective measures to meet requirements provided by the design professional.

At the final, you will be required to provide satisfactory testing by the third party contractor following the installation of the in building radio enhancement system.

-------------------

Note added to G101.  PJW Monday, September 20, 2021

 

9/20/2021 PWebb

4) Does the electrical room service meet 600v or 800a as it relates to the door being equipped with panic hardware?  NFPA 70 section 110. 

----------------

Yes, panic hardware added.  PJW Monday, September 20, 2021

9/20/2021 PWebb

5) INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:


- Fire alarm system (electronically supervised)
- Fire sprinkler system (HVLS Fans)
- Fire underground
- Kitchen hood
- Kitchen suppression system
- Fire Pump
- Radio enhancement system test.
- Radio enhancement system inspection
- Revision for CO2 Alarm, pump room rating, and emergency lights. 

 

9/20/2021 PWebb

6) Where will the carts/buggies be stored.  Demonstrate compliance with NFPA 101:36.2.5.10.

-------------

Carts/buggies are indicated outside under the canopy near the front entrance.  The egress discharge from the adjacent egress doors is shown to remain clear.  Ensure that some method is in place to ensure that they are not accidentally pushed into the egress path.   PJW Monday, September 20, 2021

9/20/2021 PWebb

7) The fire sprinkler system must be electronically supervised per NFPA 101:36.3.5.2.  This will be verified when the fire alarm shop drawings are submitted. 

---------------

Acknowledged in the RTC.  Will be addressed during the underground fire main and fire alarm reviews.  PJW Monday, September 20, 2021

9/20/2021 PWebb

8) A 150 gallon double wall diesel tank is indicated in the FP drawings for the diesel fire pump.   Provide SDS sheets for the proposed diesel fuel indicating the classification of the proposed liquid that will be used so I can verify code compliance with NFPA 1 Chapter 66.  The specifics on the tank itself will be reviewed when the fire pump is submitted.

------------------

Information provided.  PJW Monday, September 20, 2021

9/20/2021 PWebb

9) The tire storage racks are shown on the plan.  What will the aisle widths be with the tires on the racks?

------------------

Widths are indicated on sheet G101.  PJW Monday, September 20, 2021

9/20/2021 PWebb

10) A CO2 Alarm is indicated on the plans.  Provide the manufacturers specifications and installation instructions for the proposed system. 

--------------

User manual and specs provided for a Logico CO2 MK9/MK90 CO2 alarm.   However I need the plans to show a couple more things as indicated below. 

  • Show the CO2 piping on the plans.  In a conversation with the architect he believes that the CO2 is piped outside of the kitchen to the drink machines, where the bag in boxes are located.  If this is the case, a CO2 sensor/s will need to be located in the vicinity outside of the kitchen per the manual. 
  • Per the manual page 7, the central unit must be located outside of the room or area being monitored.  Currently the central unit is shown in the same room as the CO2, near the door.  The central unit cannot be located in a place where a leak could affect access to the unit. 

A hold has been placed on the building permit at insulation for a revision to address this information.  PJW Monday, September 20, 2021

9/20/2021 PWebb

11) I see a used cooking oil storage tank referenced on sheet A501.4 but I do not see the location or size of the tank.  If inside the building, show compliance with 1:66.19.7. If outside the building, indicate tank size (in gallons) and be prepared to submit for tank permit if over 60 gallons. Permit will need to show compliance with NFPA 1 Chapter 66 (1:66.9.19, 1:66.21) for a combustible IIIB liquid.

--------------------------

Specs provided for a 3.30 gallon Cleanstar 2500-CW tank with secondary containment that will be located inside.  This is not a piped system.   PJW Monday, September 20, 2021

9/20/2021 PWebb

12) Provide a door hardware schedule on the plans or the 087100 section from the project spec book.  The door hardware chart indicates the hardware classifications but no indication of what the classifications are.  Identify which doors will have card readers and how they will function.  Will it be electronic release with mechanical free egress, electric strike etc.   Also it appears that most exterior doors will be alarmed.  Will they be delayed egress.  Please clarify in the hardware schedule. 

---------------------

087100 specs have been provided.  Most all of the exterior doors will have alarmed panic.  It is indicated that hardware will be provided in the future for delayed egress.  PJW Monday, September 20, 2021 

9/20/2021 PWebb

13) Loading dock stairs require handrails on both sides.  Not clear on sheet A703.1,  NFPA 101:7.2.2.4.1.1. 

---------------------------------

Additional detail(s) has been provided but it is still not clear to me that handrails are on both sides.  Ensure that handrails are installed on both sides of all stairs per the code section above.  This will be verified at the time of final.  PJW Monday, September 20, 2021

9/20/2021 PWebb

14) The emergency lights units are indicated at 25+ feet AFF.  Provide specification sheets for the proposed lighting supporting this mounting height and spacing. 

--------------------

Specs provided for the acuity brands/Lithonia high mount emergency light.  The information provided did not indicate the mounting height/spacing or coverage of the light.  I was not able to find the light online in an attempt to find the information.  Provide manufacturers specs providing this information.  If the manufacturer does not indicate, then photometrics will be required demonstrating the required coverage (minimums, average etc). 

A hold has been placed on the permit (109 insulation) for a revision to include this information.  PJW Monday, September 20, 2021 

9/20/2021 PWebb

15) Sprinkler Criteria is provided full size on sheets FP1.0, FP2.0, FP3.0, FP4.0, FP4.1, FP4.2, FP5.0.   The sheets were provided with NRG Fire Consulting on the title block with no PE seal.  The sprinkler criteria must be sealed by a PE. 

 

An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided.  It is not a full set of shop drawing  FLORIDA ADMINISTRATIVE CODE 61G15-32.004

 

-------------------

Criteria sealed by John D. Campbell PE.  PJW Monday, September 20, 2021

9/20/2021 PWebb

16) New Comment

It was noticed during the resubmittal review that the fire pump room does not show the 1 hour rating as required by NFPA 1:13.4.2.1.1.2.  The architect is aware. 

A hold has been placed on the permit at insulation (109) for a revision to include this information.  PJW Monday, September 20, 2021

9/20/2021 PWebb