Plans for a preliminary review of a 157,522sf Class A Mercantile Occupancy that will be provided with fire sprinklers supplied by a fire pump, and a fire alarm system. There will also be a tire storage area with tire installation bays. The building is constructed as Type VB. The total occupant load is 2207.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. Reviewer: PJ Webb 904 209 1744 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
| |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
| |
|
|
1) This plan cannot be approved until a clearance sheet is issued.
|
| |
|
|
2) Sheet G101
Remove the note that states "Fire Marshal shall determine size and type of fire extinguishers". This is the responsibility of a licensed fire extinguisher contractor. FSS 633.304
|
| |
|
|
3) In Building Radio Enhancement System (BDA)
This building is required to have a third party contractor conduct a two-way radio communication test in accordance with NFPA 1:11.10 and NFPA 1221 (2016 ED.) by the time of the framing inspection.
St Johns County Fire Rescue’s radio control frequency is 853.8875. You will need to provide this information to your third party contractor.
NOTE: A copy of this report must be provided and submitted to our office as a revision before the 105 framing inspection. A 105 Framing Hold has been placed until receipt of the revision.
-If it passes the inspection radio testing at the framing stage, you will need to submit as a revision as we will record the documentation and remove the hold.
- If the third party paperwork indicates the test is not satisfactory, then the contractor will have to submit for a revision. The revision will need to include: the unsatisfactory test paperwork, outline of corrective measures, and plans to illustrate the corrective measures to meet requirements provided by the design professional.
At the final, you will be required to provide satisfactory testing by the third party contractor following the installation of the in building radio enhancement system.
|
| |
|
|
4) Does the electrical room service meet 600v or 800a as it relates to the door being equipped with panic hardware? NFPA 70 section 110.
|
| |
|
|
5) INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- Fire alarm system (electronically supervised) - Fire sprinkler system (HVLS Fans) - Fire underground - Kitchen hood - Kitchen suppression system - Fire Pump
- Radio enhancement system test.
|
| |
|
|
6) Where will the carts/buggies be stored. Demonstrate compliance with NFPA 101:36.2.5.10.
|
| |
|
|
7) The fire sprinkler system must be electronically supervised per NFPA 101:36.3.5.2. This will be verified when the fire alarm shop drawings are submitted.
|
| |
|
|
8) A 150 gallon double wall diesel tank is indicated in the FP drawings for the diesel fire pump. Provide SDS sheets for the proposed diesel fuel indicating the classification of the proposed liquid that will be used so I can verify code compliance with NFPA 1 Chapter 66. The specifics on the tank itself will be reviewed when the fire pump is submitted.
|
| |
|
|
9) The tire storage racks are shown on the plan. What will the aisle widths be with the tires on the racks?
|
| |
|
|
10) A CO2 Alarm is indicated on the plans. Provide the manufacturers specifications and installation instructions for the proposed system.
|
| |
|
|
11) I see a used cooking oil storage tank referenced on sheet A501.4 but I do not see the location or size of the tank. If inside the building, show compliance with 1:66.19.7. If outside the building, indicate tank size (in gallons) and be prepared to submit for tank permit if over 60 gallons. Permit will need to show compliance with NFPA 1 Chapter 66 (1:66.9.19, 1:66.21) for a combustible IIIB liquid.
|
| |
|
|
12) Provide a door hardware schedule on the plans or the 087100 section from the project spec book. The door hardware chart indicates the hardware classifications but no indication of what the classifications are. Identify which doors will have card readers and how they will function. Will it be electronic release with mechanical free egress, electric strike etc. Also it appears that most exterior doors will be alarmed. Will they be delayed egress. Please clarify in the hardware schedule.
|
| |
|
|
13) Loading dock stairs require handrails on both sides. Not clear on sheet A703.1, NFPA 101:7.2.2.4.1.1.
|
| |
|
|
14) The emergency lights units are indicated at 25+ feet AFF. Provide specification sheets for the proposed lighting supporting this mounting height and spacing.
|
| |
|
|
15) Sprinkler Criteria is provided full size on sheets FP1.0, FP2.0, FP3.0, FP4.0, FP4.1, FP4.2, FP5.0. The sheets were provided with NRG Fire Consulting on the title block with no PE seal. The sprinkler criteria must be sealed by a PE.
An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. It is not a full set of shop drawing FLORIDA ADMINISTRATIVE CODE 61G15-32.004
|
| |