**INFORMATIONAL ONLY NO RESPONSE NECESSARY:
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:
- Wall and ceiling finish in exit enclosure will meet Class A.
- Wall and ceiling finish in corridors will meet Class A or Class B.
- Wall and ceiling finish in other spaces will meet Class A, B or C. 101:28.3.3.
- Floor finish in exit access corridors shall be not less than Class II. 101:28.3.3.3.2
- Floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non-carpet flooring. 101:28.3.3.3.
If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.