SJC Home
Clearance Sheet C2021-005858

 Department IssuesSigned OffIntl

Plan for a new 56 device fire alarm system  that will be replacing an old system, as part of a remodel of an existing hotel.  The system will be utilizing a Starlink Firelink FACP with integrated cell dialers. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

 

1) Visible appliances must be located within 15ft of the end of corridors.  The 2 vertical corridors (as it looks on the plan) on both floors do not indicate a device within 15' from the bottom of the corridors.  If you are using room spacing rules the corridor device spacing is too great.  NFPA 72: 18.5.5.5.5., 18.5.5.5.1