Plan submitted for modification (level 2) to existing 2 story 24884sf hotel construction type IIB non sprinklered building. Scope of work: Replace doors and windows in guest units and mechanical. Replace flooring, paint walls/ceiling, lighting in bedroom and parlor. Reconfigure replace fixtures and finishes in bathrooms closets and wet bar.   Reviewed as modification to hotel option 1 using FFPC 7th edition effective January 1, 2021.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

8/16/2021 VVitori

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

8/16/2021 VVitori

Make sure existing safety features are replaced and/or functional. Included but not limited to:

- smoke detectors  NFPA 101 29.3.4.5
- tagged (within the last year) fire extinguishers at appropriate locations  NFPA 1 13.6.
- address or unit numbers in place   NFPA 1 10.12.1
- all electrical covered  NFPA 1 11.1
- self close unit fire rated door NPFA 101 29.3.6.2

8/16/2021 VVitori

A two-way radio is what allows fire fighters to talk to each other during an emergency. Several new and existing building construction msterials may not allow this communication to occur which create dead areas in this structure. There is a new law that requires a building to be tested and install a two-way radio enhancement system if the structure fails a third party communication test.  This occupancy will be required to complete the test (and possibly installation) by the dead line out lined in Florida Statute 633.202(18). If you would like to expand the scope of work to include this test let our Office know so we may provide further information.

8/16/2021 VVitori

1) Provide new hand rail detail showing compliance with 101:7.2.2.4.

Monday, August 16, 2021 Contact emailed 8x11 drawing which indicated all handrails will meet 101:7.2.2.4.

8/16/2021 VVitori

**INFORMATIONAL ONLY NO RESPONSE NECESSARY:
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- Wall and ceiling finish in exit enclosure will meet Class A.

- Wall and ceiling finish in corridors will meet Class A or Class B.

- Wall and ceiling finish in other spaces will meet Class A, B or C. 101:28.3.3.

- Floor finish in exit access corridors shall be not less than Class II. 101:28.3.3.3.2

- Floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non-carpet flooring. 101:28.3.3.3.

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

8/16/2021 VVitori