| | Department Issues | Signed Off | Intl |
|
|
Plan submitted for in building radio system. Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Reviewer: V.Vitori For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us. To schedule fire inspections call 827 6842 (automated system). Questions about inspections or resubmitting your plans call 209 1740x1.
|
| |
|
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the Permit Center. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8". - Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)
|
| |
|
|
1) The plan was designed using FFPC 6th edition. Update the code summary to illustrate the 7th edition (Dec 31, 2020) along with the correct edition of referenced Codes. FAC69a-3
NOTE: Our office reviews this to NFPA 1225.
|
| |
|
|
2) Page 2 indicates this is a 2 story structure. The plans only provide layout and coverage for the 1st and 2nd floor. This is a 3 story structure. Provide layout and coverage for the 3rd floor.
|
| |
|
|
BDA Systems shall have lightening protection that complies with NFPA 780. At this time the fire department will not review or inspect this type of system. This office requires a 3rd party inspection. Please remember installation is required to meet NFPA 780. The installing contractor will be required to provide certification documentation to the fire inspector at the time of fire final indicating compliance with NFPA 780 was met. Page 2 note 16. 1225:18.4
|
| |
|
|
3) Unable to locate where the repeater, transmitter, receiver, signal booster components, remote annunciator and operational console are listed in accord with UL 2524. 1225:18.12.1.3
|
| |
|
|
4) Where is the annunciator going? Recommend near fire alarm annunciator (usually within 10 feet of exit door). 1225:18.14.2
|
| |