1) Sprinklered reviewed and approved 1 7 22. Looking at scanned sprinkler shop drawings plan it looks like they do not meet the heads within 12" from glass or at 6' intervals as updated by the EOR in this revised FP page. Have sprinkler contractor resubmit for revision to meet new design criteria.
NOTE: Upon measurement it looks like heads are at 12' intervals and unsure of distance to wall.
Florida Administrative Code (FAC) 61G15-32.002